TECNOELETTRA s.r.l.
via D.Vioni n.5 – 42016 S. Rocco - Guastalla (RE) Tel.+39.0522.832004 Fax.+39.0522.832012
mail:
web:
www.tecnoelettra.it
Cod. Doc. MT2550041-rev.1.0 GB.doc
1 / 4
WARNING!
Check that the product delivered exactly corresponds to the ordered
one.
Installation
General information
Power electrical connections
AT206 / AT206B “Quick installation guide”
UK
Description of the data shown on the label
In =
nominal current
Imax =
maximum rated current
KA =
maximum breaking current against short circuit
Hz =
frequency
KVA =
apparent power (calculated at cos fi 0,8)
KW =
active power
HP =
horse power
V~ =
maximum use voltage of the primaries
Vaux =
maximum voltage of the auxiliary circuits
IP =
degree of protection against external agents
Kg =
approximate weight
Dim =
dimensions Height x Width x Depth
Ser.n =
serial number
Model =
product code
TECHNICAL FEATURES
Nominal voltage battery .......................................... 12Vdc
Maximum rated current ..........................................250mA
Maximum rated power ................................................ 3W
Operating range............................................... 10
17VDC
Nominal voltage generator/mains .......... 100 ÷ 265Vac L-N
Measuring range voltage appearing…………..50 ÷ 450Vac
Frequency range ............................................... 45
65Hz
Degree of protection front board................................ IP65
Degree of protection of switchboard .......................... IP20
Operating temperature................................... -20
+50°C
Storage temperature...................................... -30
+70°C
Maximum rated humidity ..........................................
90%
Single-phase
systems connections 2P
Three-phase
systems connections 4P
GENERATOR
MAINS
L N
L N
L N
LOAD
GENERATOR
MAINS
L1 L2 L3 N
LOAD
L1 L2 L3 N
L1 L2 L3 N
Cables sections
Single-phase system 2P (max 5m)
I max
min. sec.
max sec.
40A
2x 4mm²
2x 6mm²
51A
2x 4mm²
2x 6mm²
72A
2x 6mm²
2x 10mm²
89A
2x 10mm²
2x 16mm²
96A
2x 10mm²
2x 16mm²
Three-phase system 4P (max 5m)
I max
min. sec.
max. sec.
25A
1x 4mm²
1x 6mm²
32A
1x 6mm²
1x 6mm²
45A
1x 10mm²
1x 10mm²
56A
1x 16mm²
1x 16mm²
60A
1x 16mm²
1x 16mm²
Ø= 6mm
245mm
Free space of
aeration reason =
min. 10cm all around
the switchboard
Drilling template
(use the two screw anchor provided )
CT
only if
available
CT
only if
available
F1 = F6,3A
Protection for the
auxiliary battery circuits 12Vdc
F2 = F2A
Protection mains contactor
F3 = F2A
Protection generator
contactor
Internal Batterycharger with fuse
FCB = F500mA