 WARNING!

 

Check that the product delivered exactly corresponds to the ordered 

one.

 

Installation 

 

General information  

 

Power electrical connections  

 

AT206 / AT206B “Quick installation guide” 

UK 

 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Description of the data shown on the label 

 

In = 

nominal current

 

Imax = 

maximum rated current 

KA = 

maximum breaking current against short circuit  

Hz = 

frequency

 

KVA = 

apparent power (calculated at cos fi 0,8) 

KW = 

active power

 

HP = 

horse power

 

V~ = 

maximum use voltage of the primaries

  

Vaux = 

maximum voltage of the auxiliary circuits

 

IP = 

degree of protection against external agents

 

Kg = 

approximate weight

 

Dim = 

dimensions Height x Width x Depth

 

Ser.n = 

serial number

 

Model = 

product code

 

TECHNICAL FEATURES 

 
Nominal voltage battery .......................................... 12Vdc 
Maximum rated current ..........................................250mA 
Maximum rated power ................................................ 3W 
Operating range............................................... 10

17VDC 

Nominal voltage generator/mains .......... 100 ÷ 265Vac L-N 
Measuring range voltage appearing…………..50 ÷ 450Vac 
Frequency range ............................................... 45 

65Hz 

Degree of protection front board................................ IP65 
Degree of protection of switchboard .......................... IP20 
Operating temperature................................... -20 

 +50°C 

Storage temperature...................................... -30 

 +70°C 

Maximum rated humidity ..........................................

90%

 

 

 

Single-phase

 systems connections 2P 

Three-phase

 systems connections 4P 

GENERATOR 

 

MAINS 

 

L        N 

 

L        N 

 

L        N 

 

LOAD 

 

GENERATOR 

 

MAINS 

 

L1  L2  L3  N 

 

LOAD 

 

L1  L2  L3  N 

 

L1  L2  L3  N 

 

    Cables sections

 

 

Single-phase system 2P (max 5m) 

 

I max 

min. sec. 

max sec. 

40A 

2x 4mm² 

2x 6mm² 

51A 

2x 4mm² 

2x 6mm² 

72A 

2x 6mm² 

2x 10mm² 

89A 

2x 10mm² 

2x 16mm² 

96A 

2x 10mm² 

2x 16mm²

 

Three-phase system 4P (max 5m) 

 

I max 

min. sec. 

max. sec. 

25A 

1x 4mm² 

1x 6mm² 

32A 

1x 6mm² 

1x 6mm² 

45A 

1x 10mm² 

1x 10mm² 

56A 

1x 16mm² 

1x 16mm² 

60A 

1x 16mm² 

1x 16mm²

 

Ø= 6mm 

245mm 

Free space of 

aeration reason = 

min. 10cm all around 

the switchboard 

 

Drilling template 

(use the two screw anchor provided )

 

CT

 only if 

available 

CT 

only if 

available 

 

F1 = F6,3A 

Protection for  the 

auxiliary battery circuits 12Vdc 

F2 = F2A 

Protection mains contactor 

F3 = F2A 

Protection generator 

contactor 

Internal Batterycharger with fuse 
FCB = F500mA

 

Summary of Contents for AT206

Page 1: ...er 3W Operating range 10 17VDC Nominal voltage generator mains 100 265Vac L N Measuring range voltage appearing 50 450Vac Frequency range 45 65Hz Degree of protection front board IP65 Degree of protection of switchboard IP20 Operating temperature 20 50 C Storage temperature 30 70 C Maximum rated humidity 90 Single phase systems connections 2P Three phase systems connections 4P GENERATOR MAINS L N ...

Page 2: ...ch on the generator output voltage please remember to turn it in ON before the gen set start running Switchboard terminal Switchboard terminal Permanent magnet Pre excitation D Fuel electrovalve Stop electromagnet Relay Glow start plugs relay Global Special alarm function Take out the bridge if there is external emergency Relay Stop Relay Start Global Special alarm function Take out the bridge if ...

Page 3: ...splay appear OFF for 1sec the test is disabled Setup Description Range Default U 01 Automatic test interval time 1 30gg 3 gg U 02 Test duration 1 30 min 10 min U 03 Test start time 00 00 23 59 10 00 Verify that the Emergency button is released if not rotate it in clockwise direction to unlock it only if available During the first start up U11 code flashes as a reminder to programming the clock Pus...

Page 4: ...lems with this unit do not use it until you have consulted an the Retailer or Manufacturer otherwise all warranty rights will be voided This card has only to be used for the purpose for which it was specifically designed Any other use shall be considered improper and therefore dangerous All operations concerning the installation of the control panel should be carried out by skilled personnel in co...

Reviews: