ORYX202 ORYX204 ORYX208 Conventional Fire Panels
– INSTALLATION & OPERATION MANUAL
PRMAN-0047 ORYX200 S21 Fire Panel Range Rev 02.00 220224.docx
E&OE
- 35 -
3.1.2
RELAYS
The Relays have the following programmable features:
Programming
Group
Programming
Function
Comments
Options
None
Not in Use
The output is not used and will not
activate.
None
General
Fault
The output is activated when a general
fault is activated.
Output Text: 0
–21 Characters
Enabled: YES/NO
Test: YES/NO
External Fault
The output is activated when an
external fault is activated.
Output Text: 0
–21 Characters
Enabled: YES/NO
Test: YES/NO
Supply Fault
The output is activated when a supply
fault is detected.
Output Text: 0
–21 Characters
Enabled: YES/NO
Test: YES/NO
Sounder Fault
The output is activated when a
sounder fault is detected.
Output Text: 0
–21 Characters
Enabled: YES/NO
Test: YES/NO
Sounder Silenced
The output is activated when a
sounder is silenced.
Output Text: 0
–21 Characters
Enabled: YES/NO
Test: YES/NO
Sounder Activated
The output is activated when a specific
sounder is activated.
Output Text: 0
–21 Characters
Enabled: YES/NO
Test: YES/NO
Sounder Disabled
The output is activated when a
sounder is disabled.
Output Text: 0
–21 Characters
Enabled: YES/NO
Test: YES/NO
Disablement
The output is activated when an FACP
device is disabled.
Output Text: 0
–21 Characters
Enabled: YES/NO
Test: YES/NO
Test
The output is activated when an FACP
device is put into test mode.
Output Text: 0
–21 Characters
Enabled: YES/NO
Test: YES/NO
Fire
The output is activated when a general
fire alarm is activated. Repeater relay 1
default to this setting.
Output Text: 0
–21 Characters
Enabled: YES/NO
Test: YES/NO
Coincidence
The output is activated when any
2 zone fire alarms are activated.
Output Text: 0
–21 Characters
Enabled: YES/NO
Test: YES/NO
Reset
The output is activated for
approximately 10-15 seconds when the
panel is reset.
Output Text: 0
–21 Characters
Enabled: YES/NO
Test: YES/NO
Controls Enabled
The output is activated when the
controls are enabled.
Output Text: 0
–21 Characters
Enabled: YES/NO
Test: YES/NO
Supervisory
The output will activate when a
supervisory signal is detected.
Repeater relay 2 default to this setting.
Output Text: 0
–21 Characters
Enabled: YES/NO
Test: YES/NO
Fire SND
The output is activated when any fire
sounder is activated.
Output Text: 0
–21 Characters
Enabled: YES/NO
Test: YES/NO