ORYX202 ORYX204 ORYX208 Conventional Fire Panels
– INSTALLATION & OPERATION MANUAL
PRMAN-0047 ORYX200 S21 Fire Panel Range Rev 02.00 220224.docx
E&OE
- 34 -
3
PROGRAMMABLE FEATURES AND MENU STRUCTURE
The following programmable features are configured using the SOLAR software. The SOLAR software can be
downloaded from the Technoswitch website
SOLAR is a Windows application used to configure the Technoswitch ORYX and RHINO Fire Control and
Extinguishing panel ranges. The minimum operating system requirement for the SOLAR Software is Windows 7.
SOLAR uses a USB-B cable to communicate with the panels (refer to 1.9.7 USB Connection for SOLAR on
page 26).
3.1
PROGRAMMABLE FEATURES
3.1.1
ZONES
The Zones have the following programmable features:
Options
Function
Comments
Default Settings
Mode
Immediate
Zone indication and Sounders are activated
immediately. Sounder delays are cancelled.
Normal
Normal
Zone indications are activated immediately.
Sounder will only be activated after the set
sounder delay period has lapsed.
Verified
Determines the minimum time that the circuit
must be in the alarm condition before an alarm
condition is registered.
Confirmed
1st alarm from a zone is inhibited, zone is reset
and checked every 30 seconds.
If the alarm is still present after 30 seconds, the
panel generates a full fire condition.
If alarm is not present after the 30 second
continue check.
If a new alarm is received from the same zone
within 30 minutes, a full fire alarm is generated.
After 30 minutes if no alarm was received, the
confirmation check cycle will restart
Type
Normal
Normal detection only
Normal
IS (MTL 5561)
Two Channel MTL Galvanic Isolator
Enabled
Yes
Zone is enabled
Yes
No
Zone is disabled
Test
Yes
Zone is in walk test
No
No
Zone is in normal operation
Verification Time
10 to 60 seconds
Used in conjunction with verified mode. Set the
minimum time that the circuit must be alarm
condition before a fire alarm condition is
registered.
0