2.1.3
ENABLE CONTROLS
To enable controls, turn the Enable Controls key switch clockwise into the position as shown below. The
Controls Enabled LED will indicate Steady Yellow as confirmation. The key switch cannot be removed in the
Enabled position.
Controls Disabled
Controls Enabled
2.1.4
RE-SOUNDING OF SOUNDERS (EVACUATION)
▪
The following procedure is used to resound the alarm sounders:
Press and hold
for 3 seconds.
The General Fire LED and both Sounder Circuits will be on.
2.1.5
ENABLING/DISABLING OF ZONES
▪
The following procedure is used to disable a zone:
Press and hold
for 3 seconds.
The General Disable LED and Zone 1 Fault /In Test/Disable LED will both
flash rapidly Yellow.
Press
(scroll) to move on to the
zone to be disabled.
Each press of the scroll button will advance the selection onto the next
zone (i.e., two presses will select Zone 3) and this will be confirmed by the
respective Zone Fault/In Test/Disable LED flashing rapidly.
Confirm your selection by pressing
once.
The General Disable LED and the selected zone
’s Fault/In Test/Disable
LED will now be on steady Yellow. The rapid flashing LED will
automatically advance the selection onto the next zone.
To exit the enablement or disablement selection mode wait for 10 seconds
or press reset.
▪
The same procedure is used to enable a zone.
2.1.6
ENABLING/DISABLING OF SOUNDER CIRCUITS
▪
The following procedure is used to disable sounder circuits:
Press and hold
for 3 seconds.
The General Disable LED and Zone 1 Fault /In Test/Disable LED will both
flash Yellow.
Press
(scroll) to move on to the
sounder circuits to be disabled.
Each press will advance the selection onto the next zone and then after the
last zone onto the SOUNDER Fault/Disable LED. This will be confirmed by
the SOUNDER Fault/Disable LED flashing rapidly. Confirming this will
result in both Sounder Circuits being disabled.
Confirm your selection by pressing
once.
The General Disable LED, Sounder Fault/Disable LED and both SNDR
Fault LEDs will now be on steady Yellow. The rapid flashing LED will
automatically advance the selection back to zone 1.
To exit the enablement or disablement selection mode, wait for 10 seconds
or press reset.
▪
The same procedure is used to enable a sounder circuit.
2.1.7
ENABLING/DISABLING OF PROGRAMMABLE INPUT CIRCUITS
▪
Please refer to the SOLAR Help Guide (PRMAN-0049 SOLAR) to set this feature.