7
Deleting an allocation in the receiver
To delete the allocation of an address to a sensor, the corresponding address must be se-
lected (LEDs flash quickly) and then the button pressed for at least 10 seconds until the
LEDs switch over to continuous illumination.
Index specification
To process sensor values in the controller, specification and selection of the sensor address
(1-15)
and
the index (1-7) is necessary.
Indices can be specified for the following values:
Index Value
1
Room temperature
with offset values
of the +/- adjustment and the slider switch
(for evaluation “
RAS
” in the controllers UVR16x2, UVR1611 and UVR63-H from
version 7.2)
2
Measured room temperature (
without offset values
) (e.g. for UVR63)
3
Room moisture (only type RAS-F/F, otherwise the fixed value 127% is output)
4
Dew point temperature (only type RAS-F/F, otherwise the fixed value 0°C is out-
put)
5
Time in minutes since the last radio telegram (see instructions re index 5)
6
Wireless receiver quality (only displayed with X2 controllers, UVR1611 and
UVR63H from version 7.2) = Value between 0 and 1000, where 1000 represents
the maximum receiving quality (a value less than 300 can cause malfunctions). A
minus in front of this value indicates the battery is becoming weaker and must be
replaced.
7
Binary number, only for internal testing
X2 controllers:
The measured values are parameterised in the menu "
DL bus
“.
UVR1611
: The measurements are parameterised as
analog
network inputs:
NW.Node: Sensor address
Anal.NW.Outp.: Index of the measurement
Source: DL
TAPPS2 - Programming UVR1611:
A still unused network input variable must be selected for each new value.
Analog
network input
Source: DL
Sensor address
Index of the
measured value
1
3
4
2
5