7-3 Fan motor does not work while "ON" button is pressed

YES

                     NO

                   NO

 Check hardness and

 

Fit the fan motor

 

 Remove obstruction 

 various continuities

properly or

 or replace fan motor

                                   YES

replace it

 assembly

 

 Check the capacitor

 

NO

 capacity  (C)

 

 

                                   YES

 

 

 

 Check the fan motor

INTERRUPTED

 Replace the fan motor

 windings (FM)

 

 assembly

7-4 Fan works at one speed only

Check electrical connections.

NO

Fit electrical connections

Is there continuity ?

properly

                                YES

  

 Check fan motor winding

NO

 values (FM)

Replace fan motor (FM)

7-5 Poor cooling

 Is the unit cooling capacity

NO

 Suggest a more

 suitable for the room 

 powerful unit

 thermal loads ?

                                    YES

Are both air filters and heat

NO

 Clean filters and / or

exchanger cleaned ?

 heat exchanger

                                   YES

Check if difference bet-

YES

ween room air

temperature and outlet air

delivered is up to 10 °C

NO

 Low

NO

gas charge

 Proceed with

 normal operations

 foreseen for the

 above points

 fitted and if the blades can rotate

 Disconnect the unit from line. Check if the fan motor is well 

 Replace the capacitor

 The unit works properly

11

Summary of Contents for MTF73C5

Page 1: ...TECHNICAL DATA SERVICE MANUAL MTV72C5 R407C MTF73C5 R410A 0 8180 230 1 06 2003 ...

Page 2: ...4 1 Refrigerant Flow Diagram 7 5 FUNCTION 8 5 1 Room Temperature Control 8 6 PERFORMANCE DATA 9 6 1 Performance Chart 9 7 TROUBLESHOOTING 10 7 1 The unit does not work 10 7 2 Circuit breaker trips when ON button is pressed 10 7 3 Fan motor does not work while ON button is pressed 11 7 4 Fan works at one speed only 11 7 5 Poor cooling 11 7 6 Fan motor works normally but the compressor does not oper...

Page 3: ...Dimensions Weight Unit dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Volume m Weight Net kg Shipping kg Rating conditions 1 Cooling indoor air temperature 27 C d b 19 C w b 2 Dehumidification indoor air temperature 27 C d b 19 C w b 60 u r 3 Dehumidification indoor air temperature 30 C d b 27 C w b 80 u r 4 Refering data room size 100 m3 reverberation time 0...

Page 4: ...nsions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Volume m Weight Net kg Shipping kg Rating conditions 1 Cooling indoor air temperature 35 C d b 24 C w b 2 Dehumidification indoor air temperature 27 C d b 21 C w b 60 u r 3 Dehumidification indoor air temperature 30 C d b 27 C w b 80 u r 4 Refering data room size 100 m3 reverberation time 0 5 s distance 2 m Operating...

Page 5: ... capacitor compressor C2 R407C R410A µF 15 20 VAC 450 450 Heat exchanger coil Coils Rows Fin pitch mm 1 8 R407C 1 3 R410A Face area m 0 032 R407C 0 034 R410A Heat exchanger coil Coils Rows 4 R407C 5 R410A Fin pitch mm 1 8 R407C 1 3 R410A Face area m 0 072 R407C 0 067 R410A Data subject to change without notice Ω Safety devices Run capacitor operating temp Operating temperature Thermostat Coil resi...

Page 6: ...RESSOR CM BLUE BLU FAN MOTOR FM BROWN BRN INDICATING LAMP IL GREEN YELLOW GRN YEL SAFETY FLOAT SWITCH MS GRAY GRY OVERLOAD PROTECTOR OLR ORANGE ORG COMPRESSOR RELAY PR PINK PNK ON OFF SWITCH SW1 RED RED FAN SPEED SWITCH SW2 VIOLET VLT AMBIENT THERMOSTAT TA WHITE WHT TERMINAL BLOCK TP YELLOW YEL Legend of colors 6 ...

Page 7: ...4 REFRIGERANT FLOW DATA 4 1 Refrigerant flow diagram 7 ...

Page 8: ...ol is obtained by cycling the compressor ON and OFF by means of room temperature thermostat ON OFF SWITCH COMPRESSOR ON 1 5 K SET TEMPERATURE FAN SPEED SWITCH NOTE Allow 3 minutes before restarting the unit by the on off switch or thermostat knob ON ON SET SPEED 8 ...

Page 9: ...Operating characteristics with relative humidity around 50 MTV72C5 R407C MTF73C5 R410A 2 5 3 3 5 4 18 20 22 24 26 28 30 32 34 36 Room temperature C Operating current A 2 5 3 3 5 4 18 20 22 24 26 28 30 32 34 36 Room temperature C Operating current A 9 ...

Page 10: ...sed 1 2 MS contacts NO Check if the pilot NO Is the flickering alarm lamp is burnt lamp on the control Eventually replace it panel not visible 7 2 Circuit breaker trips when ON button is pressed Check the unit hardness NO Insulate the short Is it insulated circuit cable YES Check if the fan motor is NO Replace the fan motor working FM FM YES Check if compressor relay NO Fir electrical connections ...

Page 11: ... continuity properly YES Check fan motor winding NO values FM Replace fan motor FM 7 5 Poor cooling Is the unit cooling capacity NO Suggest a more suitable for the room powerful unit thermal loads YES Are both air filters and heat NO Clean filters and or exchanger cleaned heat exchanger YES Check if difference bet YES ween room air temperature and outlet air delivered is up to 10 C NO Low NO gas c...

Page 12: ...ES Check compressor Is room tempera NO The unit cannot klixon contacts ORL ture over 19 C operate below Are they open 19 C NO YES Replace the NO Check the capaci Replace the capacitor C tor capacity C thermostat YES Replace the NO Check the com YES Temperature of NO Compressor rotor compressor pressor winding compressor is locked continuity abnormally high YES Refrigerant gas Replace shortage comp...

Page 13: ...R D 28 Reyrieux BP 131 01601 Trévoux CEDEX France Tél 04 74 00 92 92 Fax 04 74 00 42 00 R C S Bourg en Bresse B 759 200 728 ...

Reviews: