7. TROUBLESHOOTING
7-1 The unit does not work
Check the voltage. Are
NO
Check the unit
YES
Check the electrical
there 198 ÷ 264 volts ?
electrical cable
supply line
YES
Check if thermostat
NO
Check the ambient
YES
contact
temperature must be
Replace the thermostat
is closed (C-2)
over 16,5°C
YES
Check if there is voltage
NO
Check if tank micro -
on the on/off switch (SW1)
switch contacts are
(contact is closed 2-4)
closed
(1 - 2 MS contacts)
NO
Check if the pilot
NO
Is the flickering alarm
lamp is burnt.
lamp on the control
Eventually replace it
panel not visible ?
7-2 Circuit breaker trips when "ON" button is pressed
Check the unit hardness
NO
Insulate the short
Is it insulated ?
circuit cable
YES
Check if the fan motor is
NO
Replace the fan motor
working (FM)
(FM)
YES
Check if compressor relay
NO
Fir electrical
connections are insulated
connections properly
YES
Check if compressor relay
YES
Replace the compressor
works. Is it in short circuit?
relay
NO
Check if compressor
YES
Replace the
windings are in
compressor
short circuit
10