BK Mikro 7 Manual
OI: BK MIKRO 7
Page 16
Rev. 2.00 dated 20.01.2006
3.1.5
Rotary switches
The two rotary switches P1 and P2 on the control unit front panel are used to
•
select the scanning mode ("Teach" or "Switch").
•
set the angular positions of the ranges, noted in degrees,
that are controlled by object monitoring or free space monitoring.
The position settings are possible in steps of 22.5°.
Fig. 3-4: Control unit – Rotary switches
The figure shows the setup on delivery.
The meaning of the rotary switches is determined by the selected scanner together with the
corresponding "Scanner" switch position.
Toggle switch
Rotary switch
Meaning
for scanner
BK7SC:
P1=0
P2=0
Scanning using teach mode
P1
≥
0
P2
>
P1
P2
≤
270
Scanning after setting scanning range
(object monitoring and free space monitoring),
at which:
P1=start position (without tolerance)
P2=end position (without tolerance)
for scanner
BK7RLSC:
P1=0
P2=0
Scanning using teach mode
0<P1<360
0<P2<360
Scanning after setting scanning ranges
(only object monitoring, no free space monitoring),
at which:
P1=range CW (rotation from stop position)
P2=range CCW (rotation from stop position)
Ranges of tolerance selectable: ±3° and ±10°
Illegal switch settings
•
P1=0 and P2
≠
0
Error
•
P1
≠
0 and P2=0
Error
will cause flashing red and green LED.
Minimum angle = 5°
The minimum distance between the object and the wand
must be an angle
of this value, so that scanning can start really, otherwise a
"K.O." fault
message will be indicated.
9 0
0
180
270
90
0
180
P1
P2