VEGA KS ( 1/2/3) KVA MANUAL
17
a)
Press and hold the OFF key for more than half a second to turn off the UPS.
b)
When turning off the UPS, it will do self-testing firstly. The LEDs light and go out
circularly and orderly until there is no display on the cover.
2-5
Configuring Battery Setings
l
Set the UPS for the number of EBPs installed.
To ensure maximum battery runtime, configure the UPS for the correct
number of EBPs, refer to Table 8 for the appropriate setting of battery numbers
and type. Use the up and down scroll keys to select the number of battery
stringsaccording to your UPS configuration:
2-6
LCD control panel
All UPS and EBP Cabinets
Number of
BatteryStrings
UPS only (internal batteries)
1(default)
UPS+1EBP
3
UPS+2EBPs
5
UPS+3EBPs
7
UPS+4EBPs
9
NOTE
The UPS contains one battery string; each EBP contains two
batterystrings.