8.
Modbus RTU Communications
8.1.
Introduction
The TECDrive E3 can be connected to a Modbus RTU network via the RJ45 connector on the front of the drive.
8.2.
Modbus RTU Specification
Protocol
Modbus RTU
Error check
CRC
Baud rate
9600bps, 19200bps, 38400bps, 57600bps, 115200bps (default)
Data format
1 start bit, 8 data bits, 1 stop bits, no parity.
Physical signal
RS 485 (2-wire)
User interface
RJ45
Supported Function Codes
03 Read Multiple Holding Registers
06 Write Single Holding Register
16 Write Multiple Holding Registers (Supported for registers 1
–
4 only)
8.3.
RJ45 Connector Configuration
For full MODBUS RTU register map
information please refer to your Invertek
Drives Sales Partner. Local contacts can be
found by visiting our website
www.invertekdrives.com
When using MODBUS control the Analog and
Digital Inputs
can be configured as shown in section 7.5
1
CAN -
2
CAN +
3
0 Volts
4
-RS485 (PC)
5
+RS485 (PC)
6
+24 Volt
7
-RS485 (Modbus RTU)
8
+RS485 (Modbus RTU)
Warning:
This is not an Ethernet
connection. Do not connect
directly to an Ethernet port.
8.4.
Modbus Register Map
Register
Number
Par.
Type
Supported
Function
Codes
Function
Range
Explanation
03 06 16
Low Byte
High Byte
1
-
R/W
✓
✓
✓
Drive Control Command
0..3
16 Bit Word.
Bit 0 : Low = Stop, High = Run Enable
Bit 1 : Low = Decel Ramp 1 (P-04), High = Decel
Ramp 2 (P-24)
Bit 2 : Low = No Function, High = Fault Reset
Bit 3 : Low
–
No Function, High = Coast Stop
Request
2
-
R/W
✓
✓
✓
Modbus Speed reference setpoint
0..5000
Setpoint frequency x10, e.g. 100 = 10.0Hz
4
-
R/W
✓
✓
✓
Acceleration and Deceleration Time
0..60000
Ramp time in seconds x 100, e.g. 250 = 2.5 seconds
6
-
R
✓
Error code
Drive status
Low Byte = Drive Error Code, see section 10.1
High Byte = Drive Status as follows :-
0 : Drive Stopped
1: Drive Running
2: Drive Tripped
7
R
✓
Output Motor Frequency
0..20000
Output frequency in Hz x10, e.g. 100 = 10.0Hz
8
R
✓
Output Motor Current
0..480
Output Motor Current in Amps x10, e.g. 10 = 1.0 Amps
11
-
R
✓
Digital input status
0..15
Indicates the status of the 4 digital inputs
Lowest Bit = 1 Input 1
20
P00-01
R
✓
Analog Input 1 value
0..1000
Analog input % of full scale x10, e.g. 1000 = 100%
21
P00-02
R
✓
Analog Input 2 value
0..1000
Analog input % of full scale x10, e.g. 1000 = 100%
22
P00-03
R
✓
Speed Reference Value
0..1000
Displays the setpoint frequency x10, e.g. 100 = 10.0Hz
23
P00-08
R
✓
DC bus voltage
0..1000
DC Bus Voltage in Volts
24
P00-09
R
✓
Drive temperature
0..100
Drive heatsink temperature in ºC
All user configurable parameters are accessible as Holding Registers, and can be Read from or Written to using the appropriate Modbus
command. The Register number for each parameter P-04 to P-60 is defined as 128 + Parameter number, e.g. for parameter P-15, the register
number is 128 + 15 = 143. Internal scaling is used on some parameters, for further details please contact your Invertek Drives Sales Partner.