Fan Configuration 

Flow Range (cfm) 

For Series B Duct Blaster

 

Open (no Flow Ring) 

1,500 - 600 

Ring 1 

              800 – 225 

Ring 2 

              300 – 90 

Ring 3 

              125 – 10  

 

 

Quick Guide DB-PR700  

 

One-Point 25 Pascal Total Leakage Duct Pressurization Test 

(blowing air into the duct system)

  

Using the Minneapolis Duct Blaster

 and DG-700 Digital Gauge 

   
 

1.

 

Connect the Duct Blaster fan to the duct system. 
a)

 

Choose a location to install the Duct Blaster fan. In single, double or triple returned systems, the largest and closest return to the 

air handler is usually the best choice. 

Note:

 In multi-return systems (a return in every room), installing at the air handler cabinet is 

often best.  

 

b)

 

Remove any remote filters from the chosen return and then connect the black square transition piece to the return using 

temporary tape. Completely seal the remaining open area of the return with 
tape.  

 

c)

 

Pull the Duct Blaster fan and flex duct out of the carrying case. Connect 

the flex duct to the 

exhaust side

 of the fan (i.e. the side with the metal 

guard) using the round transition piece and connect trim. Connect the open 
end of the flex duct to the square transition piece using the velcro strap on 
the flex duct.

 

d)

 

Connect the fan speed controller to the fan and plug it into a grounded 

power outlet.   

e)

 

Install the Flow Ring which you think best matches the needed fan flow. 

f)

 

If your DG-700 gauge and fan speed controller are compatible with Cruise Control, install the fan control cable into the 3.5 mm 

communication jacks located on top of the DG-700 and on the side of the speed controller (otherwise skip this step). ** 

 
 

2.

 

Prepare the duct system and house for the Test. 
a)

 

Adjust the HVAC system controls so that the air handler does not turn on during the Test.  

b)

 

Temporarily seal off all remaining supply and return registers, and combustion or ventilation air inlets which are connected to the 

duct system. Use 

Duct Mask

 temporary register sealing material provided with your Duct Blaster, or use painters tape and paper. 

c)

 

Turn off any exhaust fans, vented dryers, and room air conditioners. 

d)

 

Remove all central filters (i.e. in air handler or return plenum). 

e)

 

Open a door or window between the building and outside to prevent changes in building pressure when the Duct Blaster is 

running. 

f)

 

If the Duct Blaster is installed in an attic, 

garage or crawlspace - open vents or access 
panels or doors from these spaces to the outside. 

 
 

3.

 

Connect tubing to the DG-700 Pressure 
Gauge.  
a)

 

Select a location to measure duct pressure. 

The best location for measuring duct pressure is 
often in the supply trunkline or plenum. Drill a 
small hole (1/4" to 3/8" OD) into the duct to 
allow a static pressure probe to be installed. 
Install the static pressure probe with the end of 
the probe pointing into the air flow that will be 
coming from the Duct Blaster fan. If the duct 
system is reasonably airtight (e.g. less than 200 
cfm25 of leakage), duct pressures can be 
measured at any supply register by inserting a 
piece of tubing through the temporary register 
seal.   

b)

 

Connect tubing to the DG-700 as shown in 

the illustration to the right.  

 
 

**  Your DG-700 gauge is compatible with Cruise Control if the CONFIG, CLEAR, START and ENTER keys have additional red 
lettering below the main black script. Cruise Control also requires a Duct Blaster speed controller with a 3.5 mm communication jack 
installed on the side of the controller box, and a fan control cable. 

Connect the Red 
tubing to the 
Chan B Input tap. 
The other end of 
the Red tubing 
should be 
connected to the 
brass tap in the 
middle of the DB 
fan housing.  

Connect Chan A Ref 
tap to inside of 
building (if gauge is 
located in the 
building, leave this 
tap open). Be sure 
window is open.

 

Connect Chan B Ref 
tap to space where 
the fan is installed (if 
fan and gauge are in 
the same space, 
leave this tap open). 

Connect the Green (or 
Clear) tubing to the 
Chan A Input tap. The 
other end of the Green 
tubing should be 
connected to the duct 
system (by either 
inserting into a sealed 
register, or connecting 
to the end of the 
installed static 
pressure probe). 

Optional fan   
control cable         
(for Cruise Control).

 