Site Wiring Fault 

Alarm Code: 04 

Site Fault detection is 
supported on all models 
anytime there is a 
Grounding Neutral 
connection.   

Alarm triggers when the 
difference between 
ground and neutral 
voltage is > 15v.       

Site Fault detection should 
be enabled by default. It can 
still be enabled / disabled 
from the LCD settings 
menu. 

Reconnect all input wires 

Utility Abnormal 

Alarm Code: 02 

Utility is out of the 
tolerance of input 

Check input mains condition 

Back feed 

Alarm Code:93 

UPS has a unexpected 
bypass current on battery 
mode 

Transfer to maintenance 
bypass and call service. 

Battery Disconnect 

Alarm Code:11 

Battery voltage is lower 
than the batteries 
disconnected level 
defined for this UPS. This 
may be due to a blown 
fuse, intermittent battery 
connection or battery 
cable being 
disconnected. 

Verify that all batteries are 
properly connected. 

If the condition persists, 
contact your service 
representative. 

Battery low 

Alarm Code:12 

The UPS is in Battery 
mode and the battery is 
running low 

This warning is 
approximate, and the actual 
time to shutdown may vary 
significantly. 

Depending on the UPS load 
and number of Extended 
Battery Modules(EBMs), the 
“Battery Low” warning may 
occur before the batteries 
reach 25% capacity 

Service Battery 

Alarm Code:13 

A faulted battery string 
has been detected and as 
a result the battery 
charger has been 
disabled until it is 
replaced 

Contact your service 
representative 

55 

Output Overload 

Alarm Code:41 

Output is overload. 

Remove some of the 
equipment from the UPS. 
The UPS continues to 
operate, but may switch to 
Bypass mode or shutdown if 
the load increases. 
The alarm resets when the 
condition becomes inactive. 

Inv Overload Fault 

Alarm Code:42 

UPS has transferred to 
bypass or fault mode 
because of overload in 
inverter mode 

The UPS transfers to 
Battery mode if supporting 
the load. 
Remove some of the 
equipment from the UPS 

Byp Overload Fault 

Alarm Code:43 

UPS has cut off the 
output and transferred to 
fault mode because of 
overload in bypass mode 
or HE mode. 

Remove some of the 
equipment from the UPS 

Output Short Circuit 

Alarm Code:31 

Indicates that the UPS 
has detected abnormally 
low impedance placed on 
its output and considers it 
a short circuit 

Remove all the loads. Turn 
off the UPS.   

Check if UPS output and 
loads is short circuit.   

Ensure short circuit is 
removed before turning on 
again. 

Fan Failure   

Alarm Code:84 

Indicates that the fan 
could not work normally. 

Check fans of UPS 

Heatsink Over 
Temperature 

Alarm Code:81 

Indicates that the 
temperature of heatsink 
is too high, UPS will get 
over temperature fault 
soon. 

If the UPS transferred to 
Bypass mode,   

If the condition persists, 
shut down the UPS. Clear 
vents and remove any heat 
sources. Allow the UPS to 
cool. Ensure the airflow 
around the UPS is not 
restricted. Restart the UPS. 

Ambient Over 
Temperature 

Alarm Code:82 

Indicates that the ambient 
temperature is higher 
than the operation 
temperature on 
specification 

 

Summary of Contents for AP160N-10K

Page 1: ...tup 19 3 7 Installation of UPS with AC inputs 20 4 Power cables connection Startup 22 4 1 Access to terminal block 23 4 2 Common input sources connection 23 4 3 Separate input sources connection 24 4...

Page 2: ...wer problems such as power failures power sags power surges brownout and line noise Power outages can occur when you least expect them and power quality can be erratic These power problems have the po...

Page 3: ...timize recharge time l Selectable High Efficiency mode Eco Mode of operation l Start on battery capability for powering up the UPS even if utility power is not available l Standard communication optio...

Page 4: ...fety instructions and important regulatory information in your Safety Environmental and Regulatory Information document 5 neutral conductor have to be provided in the building wiring installation l Th...

Page 5: ...high short circuit current and pose a risk of shock Take all precautionary measures specified as below and any other measures necessary when working with batteries 1 Remove all jewellery wristwatches...

Page 6: ...ns and packing materials for the carrier or place of purchase and file a claim for shipping damage If you discover damage after acceptance file a claim for concealed damage Note Check the battery rech...

Page 7: ...on on each side carefully lift the cabinet out of the outer carton using the handles on the cardboard and set it on a flat stable surface see Figure 3 3 3 4 Place the cabinet in a protected area that...

Page 8: ...it for future use 3 3 UPS Rear Panel This section shows the rear panel of the Online R T models 6K model Figure 3 5A 6K Rear Panel single parallel without maintenance bypass 13 Figure 3 5B 6K PDU Rea...

Page 9: ...binets into the rack requires a minimum of two people CAUTION Removing the batteries requiered precautions which should be performed or supervised by personnel with knowledge of batteries Keep unautho...

Page 10: ...g rails in the rack then install the UPS in the sliding rail 17 Figure 3 12 Install the sliding rails 7 For 10K Install the battery pack and battery protection plate then fix the front panel Figure 3...

Page 11: ...2 Replace UPS s front panel and EBM s front panel Figure 3 15 Replace UPS s front panel and EBM s front panel 19 10K Model Figure 3 16 Plug the EBM cable into the UPS battery connector 3 6 Tower Setu...

Page 12: ...systems are identical Otherwise a transformer is necessary UPS with common Normal and Bypass AC inputs UPS with separate Normal and Bypass AC inputs Earthing systems are identical Earthing systems are...

Page 13: ...ery Cabinet Positive Pole Negative pole Min conductor cross section 4mm 2 10AWG 10mm2 6AWG External Battery Cabinet Fuse in Positive Pole Negative pole 60A 80A The UPS does not have an automatic prote...

Page 14: ...do not exceed the UPS capacity to prevent an overload alarm 1 Verify that the internal batterties are connected 2 If optional EBMs are installed verify that the EBMs are connected to the UPS 3 Set th...

Page 15: ...on the UPS display Deactivate the external REPO switch and restart the UPS 4 6 Parallel Installation and Operation 4 6 1 Brief introduction of the redundancy The parallel structure is 1 1 As long as...

Page 16: ...28 Figure 4 5 a Parallel systerm wiring diagram of 6K 10K 29 Figure 4 5 b Parallel System Installation Diagram...

Page 17: ...press the button to turn off the UPS then UPS will work in bypass mode 31 4 Set the main maintenance bypass switch from UPS to ByPass then switch off the main output breaker and the input breaker and...

Page 18: ...in menu Press this button for 1s to exit the present menu to default system status display menu without executing a command or changing a setting Scroll up Press this button for 0 1sec 1s to scroll up...

Page 19: ...operating mode or status 35 Table 5 3 Status Summary Screens Status Summary Screen Description Fig 5 3 Normal mode The UPS is operating in Normal mode from utility power Fig 5 4 Battery mode When the...

Page 20: ...bypass and keep alarming The backlight of LCD would also turn to red 37 Fig 5 11 Overload When the UPS is overload the alarm will beep twice every second Some unnecessary loads should be get rid of on...

Page 21: ...order to cut off the UPS output simply cut off the utility power supply A few seconds later LCD display shuts down and no output voltage is available from the UPS output terminal 5 3 4 Turning off UP...

Page 22: ...atus please see Fig5 14 5 4 3 The event log menu By pressing on the menu of Event log the display would enter the next event menu tree All the previous events alarm and fault have been recorded here T...

Page 23: ...menu tree 5 4 5 The control menu By pressing on the menu of Control the display would enter the next control menu tree 1 Start Battery Test this is one command that control the UPS to do the battery...

Page 24: ...press on the menu of Identification the display would enter the next identification menu tree The identification information includes UPS serial number firmware serial number model type would be show...

Page 25: ...unction loss even directly damage the load battery or UPS Most of settings could only be done while UPS is in Bypass mode Figure 5 19 Setting menu tree 47 Example set rated output voltage value Figure...

Page 26: ...disconnected from utility power 2 Place the UPS on a flat stable surface with the front of the cabinet facing you 49 3 Remove the UPS front cover 4 Disconnect the internal battery connectors 5 Fix the...

Page 27: ...chapter provides the following specifications l Model list l General Specification l Electrical Performance l Environmental and Safety 7 1 Electrical specification Model Online RT 6K Online RT 10K Ou...

Page 28: ...y are preventive alarms intended to alert the user Active alarms are accompanied by an audible buzzer The control panel provides troubleshooting information from two main menus l UPS status menu Acces...

Page 29: ...s replaced Contact your service representative 55 Output Overload Alarm Code 41 Output is overload Remove some of the equipment from the UPS The UPS continues to operate but may switch to Bypass mode...

Page 30: ...e charger until the next power recycle Contact your service representative Battery Over Voltage Alarm Code 16 Indicates that the battery voltage is too high The UPS will turn off the charger until the...

Page 31: ...itiates the saving of all data and an orderly shutdown of the equipment The cable pins for the RS 232 communication port are identified in figure 9 1 and the pin functions are described in Table 3 Fig...

Page 32: ...your UPS This unique software provides safely auto shutdown for multi computer systems while power failure With this software users can monitor and control any UPS on the same LAN no matter how far fr...

Page 33: ...62 614 08108 00...

Reviews: