TDK ZACT-ME Series Specification Sheet Download Page 1

(1/2)

005-01 / 20090226 / e9111_zact_me.fm

• All specifications are subject to change without notice.

EMC Filters for AC Power Line
For Triple-phase, Large-size Box Cased  ZACT-ME Series

FEATURES

• While reducing the filter size, the highly efficient thermal design 

allows the handling of large currents with high attenuation.

• They are highly effective at preventing both the radiation and 

penetration of EMC noise. The parts are, therefore, highly 

immune to externally generated noise and do not, themselves, 

serve as sources of radiated noise

• For the frequency band set by CISPR, attenuation is shown for 

both differential mode and common mode noise components.

• Can withstand voltages of AC.1250V between the lines, and AC. 

2000V between the line to ground.

• It is a product conforming to RoHS directive.

APPLICATIONS

Computers, HDDs, electronic exchange devices, NC control 

devices, inverters for motor, etc.

SAFETY STANDARDS

SHAPES AND DIMENSIONS

Dimensions in mm

• Case: metal, terminal: stud

ELECTRICAL CHARACTERISTICS

Conformity to RoHS Directive

Part No.

Standard and standard No.
U.S.A.

Canada

Europe

 

UL1283

CSA C22.2 No.8

EN60939

ZACT2230-ME

LR76849C

P08208997

UL

CSA

NEMKO

Part No.

A

B

C

D

E

F

øG

H

I

J

K

ZACT2230-ME

120

200

115

260

100

220

M6

5.5

64

66

240

Part No.

ZACT2230-ME

Rated voltage Eac(V)

250

Rated current(A)

30

Test voltage Eac(V)[Between terminal and case]

2000

Insulation resistance(M

)

[DC. 500V, 1min/between terminal and case]

100min.

Leakage current(mA)[250V • 60Hz]

1max.

DC resistance(m

)

40max.

Operating temperature range(°C)[Including self-temperature rise]

–25 to +85

With derating over(°C)

45

Temperature rise(°C)

35max.

Attenuation frequency range 
(MHz)[+5 to +35°C]

Differential mode at 40dB

0.15 to 10

Common mode at 40dB

0.15 to 10

Weight(kg)

5

C

J

øG

A

I

øH

E

H

B

F

D

R

1

S

1

T

1

R

2

S

2

T

2

K

• Conformity to RoHS Directive: This means that, in conformity with EU Directive 2002/95/EC, lead, cadmium, mercury, hexavalent chromium, and specific 

bromine-based flame retardants, PBB and PBDE, have not been used, except for exempted applications.

Reviews: