TPF45000 Installation Manual

ENGLISH 

General Safety Instructions: 

READ SAFETY INSTRUCTIONS     

Servicing: 

These products are not customer serviceable TDK-Lambda UK LTD and their authorised agents only are permitted 
to carry out repairs.  

Critical Components: 

These products are not authorised for use as critical components in nuclear control systems, life support systems or 
equipment for use in hazardous environments without the express written approval of the Managing Director of TDK-
Lambda EMEA. 

Product Usage: 

These products are designed for use within a host equipment which restricts access to authorised competent 
personnel.

This product is a component power supply and is only to be installed by qualified persons within other equipment and 
must be not operated as a stand alone product. 
This product is for sale to business to business customers and can be obtained via distribution channels.  
It is not intended for sale to end users. 

This product is a component power supply and does not fall within the scope of the EMC directive. Compliance with 
the EMC directive must be considered in the final installation. Please contact your local TDK-Lambda office.  

Environmental: 

These products are IPX0, and therefore chemicals/solvents, cleaning agents and other liquids must not be used. 

Environment: 

This power supply is a switch mode power supply for use in applications within a Pollution Degree 2, overvoltage 
category II environment. Material Group IIIb PCB’s are used within it. 

Output Loading: 

The output power taken from the power supply must not exceed the rating stated on the power supply label, except 
as stated in the product limitations in this handbook. 

Input Parameters: 

This product must be operated within the input parameters stated in the product limitations in this handbook. 

End of Life Disposal: 

The unit contains components that require special disposal. Make sure that the unit is properly disposed of at the 
end of its service life and in accordance with local regulations. 

RISK OF ELECTRIC SHOCK           

High Voltage Warning: 

Dangerous voltages are present within the power supply

.  

The professional installer must protect service personnel 

from inadvertent contact with these dangerous voltages in the end equipment. 

WARNING

: When installed in a Class 1 end equipment, this product must be reliably earthed and professionally 

installed. 

The unit cover(s)/chassis (where applicable) must not be made user accessible. 

The mains input connector is not acceptable for use as field wiring terminals. 

For encased products, do not use mounting screws, which penetrate the unit more than; See drawings.  

Summary of Contents for TPF45000

Page 1: ...products are IPX0 and therefore chemicals solvents cleaning agents and other liquids must not be used Environment This power supply is a switch mode power supply for use in applications within a Poll...

Page 2: ...ection Energy Hazards The main output of this product is capable of providing hazardous energy 240VA Final equipment manufacturers must provide protection to service personnel against inadvertent cont...

Page 3: ...er finalen Gesamtinstallation betrachtet werden Bitte kontaktieren Sie Ihr regionales TDK Lambda Vertriebsb ro im Falle von R ckfragen Umwelt Diese Produkte sind IPX0 aus diesem Grund d rfen keine Che...

Page 4: ...dger t vorgesehen werden Gefahren durch elektrische Energie Von bestimmten Modulen kann je nach Einstellung der Ausgangsspannung gef hrliche elektrische Energie ausgehen 240 VA Die Endger tehersteller...

Page 5: ...ter votre bureau TDK Lambda le plus proche Environnement Ces produits sont IPX0 et donc on ne doit pas utiliser des produits chimiques solvants des produits de nettoyage et d autres liquides Environne...

Page 6: ...chocs m caniques les chocs lectriques et l incendie Energies dangereuses Certains modules peuvent g n rer une nergie dangereuse 240 VA selon le r glage de tension de sortie Le fabricant de l quipement...

Page 7: ...ono a vostra disposizione per ulteriori ragguagli Condizioni ambientali Questi prodotti sono classificati come IPX0 dunque non devono essere utilizzati sostanze chimiche solventi prodotti per la puliz...

Page 8: ...cendio Pericoli energetici Alcuni moduli sono in grado di erogare energia pericolosa 240 VA a seconda della tensione in uscita impostata I produttori delle apparecchiature finali sono tenuti a protegg...

Page 9: ...mbiental Estos productos son IPX0 y por tanto no pueden utilizarse sustancias qu micas disolventes agentes de limpieza ni otros l quidos Medio ambiente Esta fuente de alimentaci n es una fuente de ali...

Page 10: ...endios Peligros de energ a Algunos m dulos pueden generar energ a peligrosa 240VA dependiendo de la configuraci n de la tensi n de salida Los fabricantes de equipos finales deben proteger al personal...

Page 11: ...to com seu escrit rio TDK Lambda mais pr ximo Ambiental Estes produtos s o IPX0 e como tal n o se devem utilizar qu micos solventes agentes de limpeza e outros l quidos Ambiente Esta fonte de alimenta...

Page 12: ...ura o da tens o de sa da O equipamento final do fabricante deve garantir que o pessoal de assist ncia est protegido contra contactos inadvertidos com estes terminais de sa da do m dulo Se essa energia...

Page 13: ...2 Ratings Specifications and Features 4 Emissions 4 Immunity 4 Maximum Ratings 5 Input Specifications 5 Output Performance Specifications 6 Protective Functions 6 Operating Modes 6 Status Indicators 7...

Page 14: ...iring terminals The appliance must be securely mounted and the Ground Stud properly bonded to the main protective earth contact before any connection to AC mains supply is made The ventilation opening...

Page 15: ...ing burning or other damage might occur to the unit The output voltage of this power supply unit is considered to be a hazardous energy level The voltage is 2V or more and the electric power is 240VA...

Page 16: ...urge IEC61000 4 5 2005 4kV common mode 2kV differential mode Conducted RF Common Mode EN61000 4 6 2009 150 kHz 80 MHz at 3 Vrms 1 kHz 80 amplitude modulated Power Frequency Magnetic Field IEC61000 4 8...

Page 17: ...rent Power allowable between 380VAC and 504VAC input 3 Critical Note If minimum load is not present while the unit is inhibited the output can slowly be charged to unsafe levels DO NOT remove output l...

Page 18: ...otective Functions Units OCP TYPE Foldback with delayed shutdown latch Manual reset by input cycling or remote control via the PMBus Interface OCP KNEE POINT 116A KNEE POINT PROTECTION NONE NO DAMAGE...

Page 19: ...the unit and the output is OFF b One or more of the Fans is rotating slow or not working at all c DC Buss in one or more of the power modules is out of limit d OTP Condition e The unit is turned OFF v...

Page 20: ...he PMBus Factory Programmed Manufacturer ID Model Revision Manufacturer location Manufacturing Date and Serial Number Table 9 Input Output and Signal Connections Input 4 Pin connector Recommended mati...

Page 21: ...for Return FAULT ALARM 7 Conducts when Fault occurs Open collector Non Polarized 60V peak Max sink current 5mADC 2 ON resistance Isolated Terminal 5 used for Return DC OK 8 Conducts when Vout is grea...

Page 22: ...TPF45000 385 POWER SUPPLY OPERATION MANUAL 10 3 February 2022 Figure 1 Pin assignments...

Page 23: ...e connected in parallel at 30cm from the output terminals along the load cable Attach a maximum 1 5m 50 coaxial cable from the ceramic capacitor electrodes to a filter attachment installed on the osci...

Page 24: ...2022 Mechanical Drawing Overall dimensions for the TPF45000 385 is shown below The unit weight is approximately 30 kg and should be installed onto a shelf or support bracket rails Secure in place usin...

Page 25: ...cale above 50 load Monitoring the Output Voltage Monitoring the Internal Temperature For reference only no accuracy specified Programming the Output ON OFF Reading and Clearing Faults Reading the Manu...

Page 26: ...4 possible addresses A6 A5 A4 A3 A2 A1 A0 R W Byte Hex Address 0 1 0 0 0 0 0 x 40h 0 1 0 0 0 0 1 x 42h 0 1 0 0 0 1 0 x 44h 0 1 0 0 0 1 1 x 46h In case more than one unit is connected to PMBus each uni...

Page 27: ...Local OPERATION ON OFF If the TPF45000 385 is turned OFF with the OPERATION OFF command it can be turned ON with the OPERATION ON command Command code Type Data sent 01h R W Byte 00h OFF 01h R W Byte...

Page 28: ...y 0 Faults Type Bit in Status Register Meaning Output behavior ON OFF FAULT 0 Global Output Enabled Output Disabled Output ONor OFF OTW WARNING 1 Internal temperature 10 C below OTP limit Output ON OT...

Page 29: ...ule 1 in OTP condition 2 1 Internal temperature of Module 2 in OTP condition 3 2 Internal temperature of Module 3 in OTP condition 4 3 Internal temperature of Module 4 in OTP condition 5 4 Internal te...

Page 30: ...1 0 Output Voltage 85 95 of Set Vout on Module 1 2 1 Output Voltage 85 95 of Set Vout on Module 2 3 2 Output Voltage 85 95 of Set Vout on Module 3 4 3 Output Voltage 85 95 of Set Vout on Module 4 5 4...

Page 31: ...ted by 1 Module Bit in 1st Byte Meaning 1 0 One InputPhase Low or Out on Module 1 2 1 One InputPhase Low or Out on Module 2 3 2 One InputPhase Low or Out on Module 3 4 3 One InputPhase Low or Out on M...

Page 32: ...FANOK Bit in the STATUS REGISTER of the TPF45000 385 Command Used Type Data bytes DFh Read Byte 1 Fan in Fault is indicated by 1 Module Bit Meaning 1 0 Fan 1 is rotating slow or Stopped 2 1 Fan 2is ro...

Page 33: ...ed Type Data bytes DEh Read Word 2 Module in Disable Mode is indicated by 1 Module Bit in 1st Byte Meaning 1 0 Vout of Module 1 Disabled 2 1 Vout of Module 2 Disabled 3 2 Vout of Module 3 Disabled 4 3...

Page 34: ...te Example Assume the data received is 0x03 0x45 03 69 3 255 69 834Hrs COMMANDSTO READ MANUFACTURING INVENTORY DETAILS Command Name Commandcode Type Data bytes PMBUS_REVISION 98h Read Byte 1 MFR_ID 99...

Page 35: ...age monitoring V 225 300 353 28233 2 Output Voltage monitoring V 0 385 25575 0 4 Output Current monitoring 0 110 100 0 0 Temperature monitoring C 0 150 23 4750 1 m b R coefficients can also be recover...

Page 36: ...ed Output voltage of the TPF45000 385 Command Used Type Data bytes 8Bh Read Word 2 READ_Iout This Command is used to retrieve the measured Output Load Current of the TPF45000 385 Command Used Type Dat...