LZSA500-3 Installation Manual

ENGLISH 

General Safety Instructions: 

READ SAFETY INSTRUCTIONS     

Servicing: 

These products are not customer serviceable TDK-Lambda UK LTD and their authorised agents only are permitted 
to carry out repairs.  

Critical Components: 

These products are not authorised for use as critical components in nuclear control systems, life support systems or 
equipment for use in hazardous environments without the express written approval of the Managing Director of TDK-
Lambda EMEA. 

Product Usage: 

These products are designed for use within a host equipment which restricts access to authorised competent 
personnel.

This product is a component power supply and is only to be installed by qualified persons within other equipment and 
must be not operated as a stand alone product. 
This product is for sale to business to business customers and can be obtained via distribution channels.  
It is not intended for sale to end users. 

This product is a component power supply and does not fall within the scope of the EMC directive. Compliance with 
the EMC directive must be considered in the final installation. Please contact your local TDK-Lambda office.  

Environmental: 

These products are IPX0, and therefore chemicals/solvents, cleaning agents and other liquids must not be used. 

Environment: 

This power supply is a switch mode power supply for use in applications within a Pollution Degree 2, overvoltage 
category II environment. Material Group IIIb PCB’s are used within it. 

Output Loading: 

The output power taken from the power supply must not exceed the rating stated on the power supply label, except 
as stated in the product limitations in this handbook. 

Input Parameters: 

This product must be operated within the input parameters stated in the product limitations in this handbook. 

End of Life Disposal: 

The unit contains components that require special disposal. Make sure that the unit is properly disposed of at the 
end of its service life and in accordance with local regulations. 

RISK OF ELECTRIC SHOCK           

High Voltage Warning: 

Dangerous voltages are present within the power supply

.  

The professional installer must protect service personnel 

from inadvertent contact with these dangerous voltages in the end equipment. 

WARNING

: When installed in a Class 1 end equipment, this product must be reliably earthed and professionally 

installed. 

The (+) or (-) output(s) can be earthed or left floating. 

The unit cover(s)/chassis (where applicable) must not be made user accessible. 

The mains input connector is not acceptable for use as field wiring terminals. 

Summary of Contents for LZS-A500-3

Page 1: ...a office Environmental These products are IPX0 and therefore chemicals solvents cleaning agents and other liquids must not be used Environment This power supply is a switch mode power supply for use i...

Page 2: ...nt for mechanical electric shock and fire hazard protection Energy Hazards The main output of this product is capable of providing hazardous energy 240VA Final equipment manufacturers must provide pro...

Page 3: ...Konformit t mit der EMV Richtlinie muss in der finalen Gesamtinstallation betrachtet werden Bitte kontaktieren Sie Ihr regionales TDK Lambda Vertriebsb ro im Falle von R ckfragen Umwelt Diese Produkt...

Page 4: ...vor der Gefahr von mechanischen Risiken Stromschl gen und Brandschutz in dem Endger t vorgesehen werden Gefahren durch elektrische Energie Von bestimmten Modulen kann je nach Einstellung der Ausgangs...

Page 5: ...ntacter votre bureau TDK Lambda le plus proche Environnement Ces produits sont IPX0 et donc on ne doit pas utiliser des produits chimiques solvants des produits de nettoyage et d autres liquides Envir...

Page 6: ...l pour assurer la protection contre les chocs m caniques les chocs lectriques et l incendie Energies dangereuses Certains modules peuvent g n rer une nergie dangereuse 240 VA selon le r glage de tensi...

Page 7: ...ana sono a vostra disposizione per ulteriori ragguagli Condizioni ambientali Questi prodotti sono classificati come IPX0 dunque non devono essere utilizzati sostanze chimiche solventi prodotti per la...

Page 8: ...sse elettriche e dai pericoli di incendio Pericoli energetici Alcuni moduli sono in grado di erogare energia pericolosa 240 VA a seconda della tensione in uscita impostata I produttori delle apparecch...

Page 9: ...contacto con su oficina local de TDK Lambda Medioambiental Estos productos son IPX0 y por tanto no pueden utilizarse sustancias qu micas disolventes agentes de limpieza ni otros l quidos Medio ambient...

Page 10: ...ra incendios de protecci n mec nica contra descargas el ctricas y contra el peligro de incendios Peligros de energ a Algunos m dulos pueden generar energ a peligrosa 240VA dependiendo de la configurac...

Page 11: ...tre em contacto com seu escrit rio TDK Lambda mais pr ximo Ambiental Estes produtos s o IPX0 e como tal n o se devem utilizar qu micos solventes agentes de limpeza e outros l quidos Ambiente Esta font...

Page 12: ...cer energia perigosa 240 VA de acordo com a configura o da tens o de sa da O equipamento final do fabricante deve garantir que o pessoal de assist ncia est protegido contra contactos inadvertidos com...

Page 13: ...LZS A500 3 POWER SUPPLY Installation Operation and Maintenance Manual IM LZSA500 3 January 2022 Revision N...

Page 14: ...rovals 2 2 RATINGS AND SPECIFICATIONS 4 3 FEATURES 5 4 GUIDE TO APPLICATION 7 4 1 Safety Notice 7 4 2 Input Voltage 7 4 3 Output Voltage 7 4 4 Overvoltage Protection Circuit Adjustment 7 4 5 Overtempe...

Page 15: ...he rating stated on the power supply label 8 Openings in the product case are designed for ventilation and must not be obstructed when the product is installed and or operated 9 Never push objects of...

Page 16: ...ine 3m Criteria A Lightning Surge IEC61000 4 5 2 kV line to GND CM Criteria A 1 kV line to line DM Criteria A Conducted RF Common Mode IEC61000 4 6 10 V m RMS 150 kHz 80 MHz 80 AM at 1kHz Power Freque...

Page 17: ...ower 84 typical 110VAC line Output Performance Specifications Units LZS A500 3 Table 4 Voltage Line Regulation 0 1 Voltage Load Regulation 0 1 Ripple and Noise 20 MHz measurement Bandwidth PARD mVP P...

Page 18: ...7 of D connector see Fig 9 Signals Isolation Pins 6 and 7 are fully isolated from all other power supply terminals Signal Logic Logic zero below 0 7 V short circuit or open circuit disables power supp...

Page 19: ...to power supply is 1 4 Requires No M4 metric hardware supplied with unit Input and Output Connections Table 11 Input Heavy duty terminal block Chassis Ground Tapped hole and screw provided in chassis...

Page 20: ...here is sufficient OVP margin with respect to the output voltage to avoid nuisance tripping 4 4 OVERVOLTAGE PROTECTION CIRCUIT ADJUSTMENT The overvoltage protection circuit provides an adjustable mean...

Page 21: ...LZS A500 3 Power Supply Figure 1 PIN Assignments for TB201 and chassis mounted D connector 5 Figures 1 800 LAMBDA 4 Revision N January 2022 Page 8...

Page 22: ...500 3 Power Supply Figure 3 Typical Remote Sense Connection Figure 2 Typical Local Sense Connection LS Local Sense S Remote Sense LS Local Sense S Remote Sense Revision N January 2022 Page 9 1 800 LAM...

Page 23: ...rnal Programming Resistor or Voltage Source Remote Sensing Figure 4 Remote Voltage Control with an External Programming Resistor or Voltage Source Local Sensing LS Local Sense S Remote Sense LS Local...

Page 24: ...LZS A500 3 Power Supply Figure 6 Parallel Operation Revision N January 2022 Page 11 1 800 LAMBDA 4...

Page 25: ...LZS A500 3 Power Supply Figure 7 Series Operation 1 800 LAMBDA 4 Revision N January 2022 Page 12...

Page 26: ...LZS A500 3 Power Supply Figure 8 Outline Drawing Revision N January 2022 Page 13 1 800 LAMBDA 4...

Page 27: ...LZS A500 3 Power Supply Figure 9 Remote Output On Off Control Figure 10 Input Good Inverter Good Output Good Signals 1 800 LAMBDA 4 Revision N January 2022 Page 14...

Reviews: