TCS QD3040 Product Manual Download Page 1

2800 Laura Lane  •  Middleton, WI 53562  |  800.288.9383  •  fax: 608.836.9044  |  www.tcsbasys.com  

v.1902.13

|

  PRODUCT 

Manual 

The QD3040 BACnet Edge connects the 

local site BACnet controller network with 

Ubiquity Cloud.

QD3040

BACnet Edge Device

BACnet® is a registered trademark 

of ASHRAE.

Summary of Contents for QD3040

Page 1: ...800 288 9383 fax 608 836 9044 www tcsbasys com v 1902 13 PRODUCT Manual The QD3040 BACnet Edge connects the local site BACnet controller network with Ubiquity Cloud QD3040 BACnet Edge Device BACnet i...

Page 2: ...BACnet controllers See ordering section Two integrated RS 485 serial ports Integrated Ethernet controller with firewall Integrated configuration web page Remotely upgradeable gateway software Contents...

Page 3: ...lso be set on a shelf or table Do not allow the mounting screws to touch the circuit board inside the enclosure When selecting a location to mount the QD3040 be sure to allow space for cable connectio...

Page 4: ...R 12VDC Rx Tx Activity LED s To Wall Outlet To Internet To Controllers Not Used Not Used Not Used QD3040 Connections Diagram NOTES 1 USB cable is provided with QD1010 and QW1010 NOTE In the middle of...

Page 5: ...ting Resistor A B REF A B REF A B REF Shield Drain Wire COM 1 COM 2 REF REF A A B B USBPORT2 USBPORT1 ETHERNET USBPORT3 USBPORT4 VIDEO AUXVIDEO 120 Terminating Resistor 1 2 3 3 4 4 4 QD3040 at end of...

Page 6: ...esistor A B REF A B A B Shield Drain Wire COM 1 COM 2 REF REF A A B B USB PORT 2 USB PORT 1 ETHERNET USB PORT 3 USB PORT 4 VIDEO AUX VIDEO 120 Terminating Resistor 1 2 3 3 4 4 4 QD3040 at end of the n...

Page 7: ...e option in the security section All Ubiquity Cloud Application software and functionality is accessed by logging into the Central Server www ubiquitysys tems net not by using this configuration page...

Page 8: ...00ms for wired networks Reties are what you expect number of tries before considering the device not communicating MAC is the local bus line address just like you set in a stat This is due to BACnet h...

Page 9: ...Proxy check box and enter all the related details in the fields that appear Once you are finished entering information in this section click the Update Commissioning Info button SECURITY INFORMATION...

Page 10: ...1 Error No Route to Host means the unit does not currently have an Ethernet connection 2 Connected means the unit is able to communicate to the Ubiquity central server BUT is not being matched up wit...

Page 11: ...kout Troubleshooting CHECKOUT 1 Be sure to check and verify all wiring before powering the QD3040 2 Apply power The Power LED will turn on 3 If the QD3040 has not been pre programmed it can be program...

Page 12: ...dicates a proper Ethernet connection RS 485 PORTS COM 1 2 Each port has the proper biasing resistors as specified by the BACnet standard Each port is also optically isolated which cleans up the signal...