R
2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com
5
occupied Cool Setpoint A Screen.
Set the occupied cool setpoint A.
occupied Cool Setpoint B Screen.
Set the occupied cool setpoint B.
occupied Cool Setpoint C Screen.
Set the occupied cool setpoint C.
occupied Cool Setpoint d Screen.
Set the occupied cool setpoint D.
Unoccupied Cool Setpoint Screen.
Set the unoccupied cool setpoint.
User Setpoint limit Screen.
Enter the
number of degrees you want the user to
be allowed to change the preset occu-
pied setpoints up or down.
override time Screen.
Enter the num-
ber of minutes (0 to 255) that the ther-
mostat will maintain occupied setpoints
when overridden.
Second Stage heat Screen.
Indicate
whether the thermostat will control a
second stage of HEAT or use w2 as a
time clock (TCLCK)output.
Second Stage heat Screen.
Choose
whether the thermostat will control a
second stage of heating. (Select NO if
not using a second stage of heating.)
Second Stage Cool Screen.
Choose
whether the thermostat will control a
second stage of cooling. (Select NO if
not using a second stage of cooling.)
heat Stage 1 offset Screen.
Enter an
offset value for heat stage 1. First stage
is normally 0 offset.
heat Stage 1 differential Screen.
Enter a differential value for heat stage
1.
program
setup
OCCUPIED COOL
SETPOINT B: 75F
16.
program
setup
OCCUPIED COOL
SETPOINT A: 75F
15.
program
setup
OCCUPIED COOL
SETPOINT C: 75F
17.
program
setup
OCCUPIED COOL
SETPOINT D: 75F
18.
program
setup
SET OVERRIDE
TIME: 180 MINUTES
21.
program
setup
UNOCCUPIED COOL
SETPOINT:
80F
19
program
setup
LIMIT SETPOINT
/-: 05F
20.
program
setup
STAGE 2 HEAT
USED FOR HEAT
22.
program
setup
ENABLE SECOND
STAGE COOL? YES
24.
program
setup
HEAT STAGE 1
DIFF:
01F
26.
program
setup
HEAT STAGE 1
OFFSET:
00F
25.
heat Stage 2 offset Screen.
Enter an
offset value for heat stage 2. This screen
only appears if heat stage 2 is enabled
as heat.
heat Stage 2 differential Screen.
Enter
a differential value for heat stage 2. This
screen only appears if heat stage 2 is
enabled.
Cool Stage 1 offset Screen.
Enter an
offset value for cool stage 1. First stage
is normally 0 offset.
Cool Stage 1 differential Screen.
Enter
a differential value for cool stage 1.
Cool Stage 2 offset Screen.
Enter an
offset value for cool stage 2. This screen
only appears if cool stage 2 is enabled.
Cool Stage 2 differential Screen.
Enter
a differential value for cool stage 2. This
screen only appears if cool stage 2 is
enabled.
Cool Stage 3 offset Screen.
Enter an
offset value for cool stage 3. This screen
only appears if cool stage 3 is enabled.
Cool Stage 3 differential Screen.
Enter
a differential value for cool stage 3. This
screen only appears if cool stage 3 is
enabled.
Control mode Screen.
Enter whether
you want to control by temperature
only (P) or add a time factor (P+I). This
applies to the stage outputs only.
time Clock output Screen.
Choose
whether the auxiliary output will be
OPEN during occupied periods (and
closed during unoccupied periods) or
CLOSED during occupied periods (and
open during unoccupied periods).
outdoor Air Sensor Function Screen.
Choose whether or not you are using an
outdoor air sensor function. To monitor
only, select NO. See setup instructions
for dipswitch settings which must also
be set.
Cooling lockout Screen.
Enter an
outdoor air cooling lockout temperature.
This screen will not appear if the outdoor
air sensor function is disabled.
program
setup
COOL STAGE 1
DIFF:
01F
30.
program
setup
COOL STAGE 2
OFFSET:
01F
31.
program
setup
COOL STAGE 1
OFFSET:
00F
29.
program
setup
HEAT STAGE 2
DIFF:
01F
28.
program
setup
SET CONTROL
MODE:
P
35
program
setup
COOL STAGE 2
DIFF:
01F
32.
program
setup
ENABLE OUTDOOR
AIR FUNCT.? YES
37.
program
setup
COOLING LOCKOUT
TEMP: 065F
38.
program
setup
ENABLE SECOND
STAGE HEAT? YES
23.
HEAT STAGE 2
OFFSET:
01F
27.
program
setup
program
setup
TIME CLOCK
OCCUPIED:
OPEN
36.
program
setup
COOL STAGE 3
OFFSET:
01F
33.
program
setup
COOL STAGE 3
DIFF:
01F
34.