KLC/KLCUL
Installation
Guide
TCI, LLC
7878 North 86th Street
Milwaukee, WI 53224
Ph: 800-TCI-8282
www.transcoil.com
Version 1.5
Part # 25389
Apr. 2, 2012
TCI, LLC
7878 North 86th Street
Milwaukee, WI 53224
Ph: 800-TCI-8282
www.transcoil.com
Field Wiring
KLCUL Field Wiring Connection Terminals
Compression type terminals are provided
for all line wiring connections. The wire size
capacity ranges and tightening torque for
the power terminals are listed in the table.
Warnings and Cautions
Dangerous Voltage Warning: warns of
situations in which a high voltage can
cause injury and/or equipment damage.
The text next to this symbol describes
ways to avoid danger.
General Warning: warns of situations
that can cause physical injury and/
or equipment damage by means other
than electrical. The text next to this
symbol describes ways to avoid the
danger.
General Safety Instructions
Be sure to read, understand, and follow
all safety instructions.
Only qualified electricians should
carry out all electrical installation and
maintenance work on output filter.
All wiring must be in accordance with
the National Electrical Code (NEC)
and/or any other codes that apply to
the installation site.
Disconnect all power before working
on the equipment. Do not attempt any
work on a powered output filter.
The KLC, VFD, motor, and other
connected equipment must be properly
grounded.
The VFD terminals and connected
cables are at a dangerously high voltage
when power is applied to the VFD,
regardless of motor operation.
Warning
Warning
Warning
Warning
Warning
Warning
Warning
Warning
!
!
!
!
See www.transcoil.com for dimension tables
Please contact TCI Technical Support
or your TCI distributor for application
information regarding the use of KLC
output filters on the output side of the VFD.
KLCUL Model
Numbers
Input and Output Motor Power
Wire Size
Torque
(in. - lb.)
KLCUL2A to
KLCUL12A
12 - 18
10
KLCUL16A to
KLCUL55A
4 - 18
20
KLCUL80A
1 - 22
35
KLCUL110A to
KLCUL130A
2/0 - 6
120
KLCUL160A to
KLCUL200A
250 MCM - 6
275
KLCUL250A to
KLCUL300A
600 MCM - 4
Two: 250 MCM - 1/0
500
KLCUL360A
Two: 350 MCM - 4
275
KLCUL420A to
KLCUL600A
Two: 600 MCM - 2
500
KLCUL750A
Two: 800 MCM - 300
MCM