![TBB power Kinergier Pro Series Manual Download Page 38](http://html2.mh-extra.com/html/tbb-power/kinergier-pro-series/kinergier-pro-series_manual_4375271038.webp)
Kinergier Pro User Manual
33
1-OverLoad/OT
2-INV Fault
3-ACin Error
4-ACin Charging
5-ACin Ready
6-ACin Voltage
7-Fan Running
8-
MPPT/ACin CHG
9- PV Voltage
10- BMS Alarm
11-SOC Normal
2-AGS Driver
Both relay 1 and 2 will perform as AGS driver. Please
refer to 5.6.3 for explanation in details.
Relay1 Define
Display if Function Mode is '1-User Define'
Relay2 Define
Display if Function Mode is '1-User Define'
AGS Logic
Display if Function Mode is '2-AGS Driver '
5.6.3 AGS Driver
With this menu, relay 1 and relay 2 will be programmed to control the start and stop of generator.
Please find the following chart with detailed definition.
AGS Driver Set Table
>AGS Driver Set
>Relay1 Driver
Relay2 Driver
>Signal Type
Turn_On Delay
Signal Type
0-Level
Signal Type
>Turn_On Delay
>Turn_Off Delay
Turn_Off Delay
0~180s
<Back>
Signal Type
1-Pulse
>Pulse Time
Pulse Time
1~180s
<Back>
Turn_On Delay
0~180s