Kinergier Pro User Manual
21
5.5.2 Parameter set
A password is required when entering the parameter setting interface. The default is '1000' and it
can be changed. This menu contains the following sub-menus for settings:
>Parameter Set
>Para_System
Para_Mode
>Para_Battery
Para_Inverter
>Para_ACin
Change Password
>Setup Wizard
Reset Parameter
>Error Shielding
5.5.2.1 Para_System – system parameter setting
There are total three sub-menus including
Parallel_System, Solar_System and BMS_System.
“Parallel System”
sub-menu offers you all the parameters you need to configure when you are
using Kinergier Pro to compose a single phase parallel system or three phase systems.
When you are composing a single phase system, max 3 units of Kinergier Pro can be
connected together.
When you are composing a three phase system, max 9 units of Kinergier Pro can be
connected together with 3 units on each phase.
Parallel_System:
Parallel
System
Item
Setting range
Description
Parallel_System
0-Stand-alone
1-Parallel
2-Three-phase
Set the unit's in a stand alone or
parallel or three phase system.
Defaul
:0-Stand-alone
Parallel_UVW
1-U(L1)
2-V(L2)
3-W(L3)
Set the unit's phase
Default
:1-U(L1)
Parallel_Address
1~3
Can not set in a stand alone
system.
Default
:1
Redundant_Mode
0- Disable
1- Enable
This function is designed for a
power backup system ONLY. After
enabling this function, once the
master inverter fails in a parallel
system, a new master inverter will
be appointed without system
failure.
Default:
0- Disable