X4 AC Drive User’s Manual
Chapter 7: X4 Parameters
1428D-0607
- 68 -
© 2007 TB Wood’s All Rights Reserved
727 MOL Configure
Default: MOL
Range: n/a
Level 2
Parameter Value
Description
Preset 1
Preset Speed Input 1 (PS1).
Preset 2
Preset Speed Input 2 (PS2).
Preset 3
Preset Speed Input 3 (PS3).
Coast Stop
Activates a Coast-to-Stop condition.
DC Inject
Begins DC injection braking.
Loc/Rem
Switches from Local to Remote mode.
Alt Ramp
Activates Alternate Ramp.
Fault Reset
Resets a fault.
EMOP+
EMOP increases speed.
EMOP-
EMOP decreases speed.
PID Enable
Enables PI control.
Ref Switch
Switches speed reference signals.
Cur Lim Dis
Disables Current Limit mode.
SL Override
Takes control away from the serial link.
Seq 1
Sequencer input 1.
Seq 2
Sequencer input 2.
Seq 3
Sequencer input 3.
Seq Dwell
Sequencer dwell mode (pause).
Seq Advance
Sequencer advance (skip).
FLY Dis
Disable Catch-on-fly operation.
CurLimIMax
Maximum current limit value is selected when input is active.
MOL
Motor Overload input for external customer connection.
801 Program Number
Default: 0
Range: 0 to 9999
Level 2, Macro
This parameter (Special Program Number) provides a way of enabling hidden functions in the drive and storing
parameters to the customer set.
Data Value
Special Function Configured
0
Standard program
1
Reset all parameters to factory default values (display = SETP).
2
Store customer parameter values (display = STOC).
3
Load customer parameter values (display = SETC).
4
Swap active parameters with customer stored settings.
10
Reset Total Run Time, parameter 108.
Table 7-2: Description of X4 Parameters (Page 19 of 26)