2-16
CONTROLS
Models C712/C713
Controls
2
Beater Stir Cycles
Standby
When the machine is in the Standby mode, the stir cycle
will be activated. The beater stir cycle timer counts down
2 minutes (in seconds) and then activates the beater
motor for 6 seconds. After the stir cycle, the process will
repeat itself; the timer will count down
2 minutes, and the beater will run for 6 seconds.
Hopper Temperature
The hopper temperature setpoint range is 29.5°F to 39°F
(-1.4°C to 3.9°C). In the Auto or Standby mode, the
compressor starts when the hopper temperature is above
the setpoint and stops when the hopper temperature
reaches the setpoint -2°.