97
6.1 Switching
Closing
To close the ISM main contacts the CM close command shall be applied. It is a “dry contact“ input so no
external voltage should be applied.
The Close command will be accepted if:
CM state is “Ready” (Ready LED flashes green);
no Trip command is applied;
optional electrical interlock is unlocked;
mechanical and electrical interlock is unlocked (in case of ISM15_LD_8, ISM15_MD_1, ISM15_MD_3,
ISM15_Shell_2 and ISM15_HD_1 only).
If Close command is applied and held be
fore the CM is in a “Ready“ state the Close command will not be
accepted. If auxiliary power is not available, the manual generator CBunit_ManGen shall be used to charge
the CM capacitors and to close the ISM. Mechanical closing is not possible.
1. Close command input
2. Trip command input
Figure 156
CM_16 close and trip inputs
If Manual generators CBunit_ManGen are used to charge the CM, the Manual generator handle shall be
rotated until the Ready LED of the CM flashes green (approximately 30 seconds). Then the ISM close
command can be applied to the CM. One possible variant is the connection of NO and Common contacts of
relay Ready to the Close command input of the CM. Be aware that in this case the ISM will be closed
automatically once the CM reaches the Ready state.
Figure 157
CM_16 power supply connection
If Manual generators CBunit_ManGen are used for charging the CM, DC voltage outputs of the Manual
generator shall be connected to the power supply inputs (Figure 157) of CM_16_1. Pay special attention to
the correct polarity for CM_16_1(Par1_60.1_Par2_Par3_Par4_Par5).
Summary of Contents for VCB Series
Page 1: ...COMPATIBLE SERIES USER GUIDE...
Page 2: ......
Page 4: ......
Page 5: ...1 Product description...
Page 13: ...13 2 Nameplates and seals...
Page 18: ...18 3 Product handling...
Page 37: ...4 Installation...
Page 87: ......
Page 88: ...5 Commissioning...
Page 94: ...94 Figure 155 The connection points of the contact resistance meter...
Page 95: ......
Page 96: ...6 Operation...
Page 100: ...7 Maintenance and troubleshooting...
Page 105: ......
Page 106: ...8 Disposal...
Page 109: ...109 Appendix 2 Overall Drawings...
Page 112: ...112 ISM15_LD_3 Weight 13 kg ISM15_LD_6 PCD 133 mm Weight 55 kg...
Page 113: ...113 ISM15_LD_8 PCD 210 mm Weight 26 kg...
Page 114: ...114 ISM15_MD_1 150_L PCD 150 mm Weight 33 kg ISM15_MD_1 210_L PCD 210 mm Weight 35 kg...
Page 115: ...115 ISM15_MD_3 Weight 13 kg ISM15_Shell_2 150_L PCD 150 mm Weight 51 kg...
Page 120: ...120 ISM15_HD_1 275 PCD 275 mm Weight 72 kg ISM25_LD_1 210_Par2 PCD 210 mm Weight 36 kg...
Page 123: ...123 ISM25_LD_2 2 PCD 150 mm Weight 37 kg ISM25_LD_3 Weight 14 kg...
Page 125: ...125 Dimensions of Control Module CM_16_1 Par1_Par2_Par3_Par4_Par5 Weight 1 kg...
Page 127: ...127 Dimensions of Interlocking Kits CBkit_Interlock_1 CBkit_Interlock_3...
Page 128: ...128 CBkit_Interlock_4 CBkit_Interlock_5...
Page 129: ...Appendix 3 Secondary Schemes...
Page 130: ...130...
Page 131: ...131...
Page 132: ...132...
Page 133: ...133...
Page 134: ...134...
Page 135: ...135...
Page 136: ...136...
Page 137: ...137...
Page 138: ...138...
Page 139: ...139...
Page 140: ...140...
Page 142: ...Bartlett...