80
7.1 Maintenance
The Rec15/25 is a maintenance free device. No regular maintenance operations are required during the
entire period of operation.
7.2 Troubleshooting
NOTE!
In case the actions listed below do not help, contact your nearest Tavrida Electric representative.
WARNING!
All replacement operations of the HV assembly equipment require power line de-energizing. All
necessary precautions (visible line gaps, temporary groundings etc.) should be applied.
PCI Connection Problems
7.2.1
NOTE!
In case there are problems connecting to the device via the PCI interface check the following.
Possible reason
Malfunction identification procedure
Corrective action
RCM is shutdown
Check that secondary power supply switches are in
ON position
Check the voltage on power supply inputs of the RCM
The voltage shall be in the range 85-265 V.
In case the voltage at the secondary power supply
inputs of the RCM is absent, find the reasons of the
malfunction similar to “Loss of auxiliary supply”
described in paragraph labeled Loss of AC supply
Improper connection to
Rec15/25 via PCI
Check the connection according to chapter 6.5.1 of
this guide
It is no malfunction
RCM malfunction
The most likely reason for malfunction in a control
cubicle if no other reason was identified.
Replace the RCM
CPM Malfunction
7.2.2
NOTE!
If it is possible to connect to the device via the PCI interface but the CPM doesn’t work properly,
check the following.
Possible reason
Malfunction identification procedure
Corrective action
Low or no contrast of the screen
Check if LEDs on the CPM are lit
Check if the screen lights but no readings are visible
Push the button “Contrast” several times till the
readings become clearly visible
It is no malfunction
The CPM mode is disabled via PCI
Download System settings from the RCM.
Check in section “Configuration” the CPM mode
The CPM mode is disabled if the check box is not ticked
Activate CPM mode via PCI
Improper connection of plugs
connecting the CPM and the RCM
Check the connection of the plug “1” and plug “19”
Provide reliable connection of the plugs
“1” and “19”
RCM malfunction
Connect new CPM via new wiring to the RCM
If the new CPM with new wiring doesn’t work properly
it is most likely a malfunction of the RCM
Replace the RCM
Malfunction of wiring connecting the
RCM and the CPM
If the new CPM with new wiring works properly, replace
the new wiring with the old one
If the new CPM doesn’t work properly with the old wiring
it is a wiring malfunction
Replace wiring
CPM malfunction
If the new CPM works properly with the old wiring it is
CPM malfunction
Replace the CPM
Summary of Contents for Rec15/25 Al1 5p
Page 1: ......
Page 8: ......
Page 9: ...1 Product Description...
Page 15: ...15 Figure 11 CPM control and indication functions...
Page 25: ...2 Nameplates and Seals...
Page 29: ...3 Product Handling...
Page 42: ......
Page 43: ...4 Installation...
Page 57: ...5 Commissioning...
Page 60: ......
Page 61: ...6 Operation...
Page 78: ...78...
Page 79: ...7 Maintenance and Troubleshooting...
Page 93: ...8 Disposal...
Page 95: ...9 Appendices...
Page 98: ...98 Appendix 2 RC5_4 Drawings Figure 97 Dimensions of RC5_4...
Page 102: ...102 Figure 103 Dimensions of standard OSM mounting kit arrangement for lateral installation...
Page 103: ...103 Figure 104 Dimensions of interface bracket...
Page 104: ...104 Figure 105 Dimensions of OSM mounting kit with M16 pole interface front installation...
Page 105: ...105 Figure 106 Dimensions of OSM mounting kit with M16 pole interface lateral installation...
Page 106: ...106 Figure 107 Dimensions of OSM mounting kit with M20 pole interface front installation...
Page 107: ...107 Figure 108 Dimensions of OSM mounting kit with M20 pole interface lateral installation...
Page 118: ...118 Figure 119 Dimensions of OSM substation mounting kit...
Page 119: ...119 Figure 120 Dimensions of OSM substation mounting kit...
Page 122: ...122 Figure 123 Dimensions of RC mounting kit for through the pole installation...
Page 123: ...123 Figure 124 Dimensions of RC substation mounting kit...
Page 124: ...124 Figure 125 Dimensions of VT mounting kit One VT holder...
Page 132: ...132 Appendix 5 RC5_4 Wiring Diagram Figure 139 RC5_4 wiring diagram...
Page 135: ...135...
Page 136: ......