55
Figure 56
NEMA4 connector with bird protection
All technical parameters are met without the protective covers installed.
Protective covers and NEMA terminals allows multidirectional primary line wires-to-terminals connection.
4.2.5.4
Burndy® NEMA2 Connectors
Two-hole Burndy
®
connectors (Figure 57) provide a reliable connection to power line of any type of
conductors treated correspondingly. The connectors are made of Sn-Bi coated brass.
Figure 57
Two-hole
Burndy® NEMA connector
Connecting RC5_4 to Auxiliary Supply
4.2.6
ATTENTION!
Auxiliary supply VT connection wire should not be earthed inside the VT secondary
compartment.
Before the auxiliary supply from a pole mounted VT is connected to the RC5_4, resistance measurement
should be performed. Switch digital Multi-meter to the Ohm metering mode and enable beeping signal.
Connect one electrode to the earthing bar (with the connected VT base earthing bar) and second electrode
to both connection wires (one by one or to both of them simultaneously). Resistance should be infinite,
sound signal should not appear.
Resistance measurement is not performed in case an external AC/DC supply is used.
ATTENTION!
Corresponding AC1 and AC2 earthing jumpers should be removed before external AC/DC
source with predefined neutral is connected to the RC5_4.
After the main line is powered, the commissioning engineer should make sure that the auxiliary supply is
connected correctly. The auxiliary supply voltage should be checked by digital voltmeter.
Summary of Contents for Rec15/25 Al1 5p
Page 1: ......
Page 8: ......
Page 9: ...1 Product Description...
Page 15: ...15 Figure 11 CPM control and indication functions...
Page 25: ...2 Nameplates and Seals...
Page 29: ...3 Product Handling...
Page 42: ......
Page 43: ...4 Installation...
Page 57: ...5 Commissioning...
Page 60: ......
Page 61: ...6 Operation...
Page 78: ...78...
Page 79: ...7 Maintenance and Troubleshooting...
Page 93: ...8 Disposal...
Page 95: ...9 Appendices...
Page 98: ...98 Appendix 2 RC5_4 Drawings Figure 97 Dimensions of RC5_4...
Page 102: ...102 Figure 103 Dimensions of standard OSM mounting kit arrangement for lateral installation...
Page 103: ...103 Figure 104 Dimensions of interface bracket...
Page 104: ...104 Figure 105 Dimensions of OSM mounting kit with M16 pole interface front installation...
Page 105: ...105 Figure 106 Dimensions of OSM mounting kit with M16 pole interface lateral installation...
Page 106: ...106 Figure 107 Dimensions of OSM mounting kit with M20 pole interface front installation...
Page 107: ...107 Figure 108 Dimensions of OSM mounting kit with M20 pole interface lateral installation...
Page 118: ...118 Figure 119 Dimensions of OSM substation mounting kit...
Page 119: ...119 Figure 120 Dimensions of OSM substation mounting kit...
Page 122: ...122 Figure 123 Dimensions of RC mounting kit for through the pole installation...
Page 123: ...123 Figure 124 Dimensions of RC substation mounting kit...
Page 124: ...124 Figure 125 Dimensions of VT mounting kit One VT holder...
Page 132: ...132 Appendix 5 RC5_4 Wiring Diagram Figure 139 RC5_4 wiring diagram...
Page 135: ...135...
Page 136: ......