7.2.3.8
Excessive Close Time
Possible reason
Malfunction identification procedure
Corrective action
OSM coil short/open circuit
Check if the reading in the malfunction log “OSM coil
short circuit” is present
Fix the “OSM coil short circuit” (refer to
7.2.3.10
) or “OSM coil open circuit”
(refer to 7.2.3.9) malfunction first
Driver is not ready
Check that the malfunction “Driver is not ready” is
present
Wait for 1 min and open the OSM
The “Excessive close time malfunction”
will disappear
RCM malfunction
Switch off the RC5_4 and battery
Disconnect plug „8“ from the RCM
The indication of main contact position should
change to “Close”
If the indication doesn’t change to “Close” the
malfunction is in the RCM
Replace the RCM
Short circuit in the wiring connecting the
RCM with control cable
Switch off the RC5_4 and the battery
Disconnect the control cable from the RC5_4.
Switch on the RC5_4 and battery
The indication of main contact position should
change to “Close”
If the indication
doesn’t change to “Close” the
malfunction is in the wiring connecting the RCM with
control cable
Replace the RC5_4
Open circuit in Control Cable
Switch off the RC5_4 and the battery
Connect the control cable to the RC5_4.
Disconnect the control cable from the OSM
Switch on the RC5_4 and the battery
The indication of the main contact position should
change to
“Close”
If the indication doesn’t change to “Close” the
malfunction is in the control cable
Replace the control cable
OSM malfunction
If none of the above described actions helped it is
an OSM malfunction
Replace the OSM
7.2.3.9
OSM Coil Isolated
Possible reason
Malfunction identification procedure
Corrective action
The OSM is switched off manually
Check if the OSM is switched off manually.
Return the
OSM to “operated” position.
Wiring connecting drivers of the RCM
and control cable are not properly
connected
Check that wiring connecting the drivers of the RCM
and control cable are properly connected
Connect wiring properly
The RCM malfunction
Switch off the RC5_4 and the battery and wait for 2
minutes
Short circuit inputs 1 and 2 of plug “8” of the RCM
(Figure 81)
Switch on the RC5_4 and the battery
The malfunction readings should change to
“OSM
coil short circuit”
In case the reading doesn’t change the malfunction
is in the RCM
NOTE!
Remove the short circuiting wiring after the
test. Connect the wiring to the drivers properly.
Replace the RCM
Wiring assembly in the RC5_4 is open
circuited
Switch off the RC5_4 and the battery and wait for 2
minutes
Replace the RC5_4
Summary of Contents for Rec15/25 Al1 5p
Page 1: ......
Page 8: ......
Page 9: ...1 Product Description...
Page 15: ...15 Figure 11 CPM control and indication functions...
Page 25: ...2 Nameplates and Seals...
Page 29: ...3 Product Handling...
Page 42: ......
Page 43: ...4 Installation...
Page 57: ...5 Commissioning...
Page 60: ......
Page 61: ...6 Operation...
Page 78: ...78...
Page 79: ...7 Maintenance and Troubleshooting...
Page 93: ...8 Disposal...
Page 95: ...9 Appendices...
Page 98: ...98 Appendix 2 RC5_4 Drawings Figure 97 Dimensions of RC5_4...
Page 102: ...102 Figure 103 Dimensions of standard OSM mounting kit arrangement for lateral installation...
Page 103: ...103 Figure 104 Dimensions of interface bracket...
Page 104: ...104 Figure 105 Dimensions of OSM mounting kit with M16 pole interface front installation...
Page 105: ...105 Figure 106 Dimensions of OSM mounting kit with M16 pole interface lateral installation...
Page 106: ...106 Figure 107 Dimensions of OSM mounting kit with M20 pole interface front installation...
Page 107: ...107 Figure 108 Dimensions of OSM mounting kit with M20 pole interface lateral installation...
Page 118: ...118 Figure 119 Dimensions of OSM substation mounting kit...
Page 119: ...119 Figure 120 Dimensions of OSM substation mounting kit...
Page 122: ...122 Figure 123 Dimensions of RC mounting kit for through the pole installation...
Page 123: ...123 Figure 124 Dimensions of RC substation mounting kit...
Page 124: ...124 Figure 125 Dimensions of VT mounting kit One VT holder...
Page 132: ...132 Appendix 5 RC5_4 Wiring Diagram Figure 139 RC5_4 wiring diagram...
Page 135: ...135...
Page 136: ......