23
Table 8
– Input/Output Module (IOM) parameters
Digital inputs
Value
Rated voltages of signal applied to digital inputs
- for IOM-04
- for IOM-03
12/24/30/48/60 V DC
110/125/220 V DC
Pickup voltage of signal applied to digital inputs
- for IOM-04
- for IOM-03
Above 7 V
Above 100 V
Reset voltage
- for IOM-04
- for IOM-03
Below 3 V
Below 30 V
Maximum continuous voltage of signal applied to digital inputs
- for IOM-04
- for IOM-03
75 V
275 V
Input resistance
- for IOM-04
- for IOM-03
3 kOhm
125 kOhm
Recognition time, ms - not more
20
Reset time, ms - not more
20
Digital outputs
Value
Rated voltage
250 V AC
Rated current
16 A
Breaking capacity DC1 (at L/R=1ms): 30/110/220 V
16/0.3/0.12 A
Minimum switching load
500 mW (10V/5mA)
Table 9
– Wired Ethernet module (ETH) parameters
Parameter
Value
Applicable standard
USB 1.2 (according to RC5 specification)
IEEE 802.3 10Base-T
IEEE 802.3u 100Base-T
IEEE 802.3x Flow Control
Interface
RJ-45 10/100 Ethernet port
Maximum receive / transmit speed
Up to 70 Mbps (full duplex mode)
Dimensions
60.2 x 50 x 37.6 mm
Net weight, not more
25 g
Power consumptions
1.0 W (max)
Operation temperature
-
40…+85 °C
Table 10
– Optical Ethernet module (ETH) parameters
Parameter
Value
Applicable standard
USB 1.2 (according to RC5 specification)
IEE802.3u 100Base-FX
IEC 9314-3: 1990
ANSI X3.166-1990
Interface
SC/ST
Maximum receive / transmit speed
100
–125 Mbps (full duplex mode)
Dimensions
132 x 71 x 39 mm
Net weight, not more
115 g
Power consumptions
1.0 W (max)
Operation temperature
-
40…+85 °C
Table 11
– Bluetooth module (BTM) parameters
Parameter
Value
Bluetooth version
2.0
Frequency
2402 … 2485 MHz
Channel intervals
1 MHz
Operation radius
10 m
Operation mode
Slave
Profile
Serial port
Tx Power
+6 dBm
Summary of Contents for Rec15/25 Al1 5p
Page 1: ......
Page 8: ......
Page 9: ...1 Product Description...
Page 15: ...15 Figure 11 CPM control and indication functions...
Page 25: ...2 Nameplates and Seals...
Page 29: ...3 Product Handling...
Page 42: ......
Page 43: ...4 Installation...
Page 57: ...5 Commissioning...
Page 60: ......
Page 61: ...6 Operation...
Page 78: ...78...
Page 79: ...7 Maintenance and Troubleshooting...
Page 93: ...8 Disposal...
Page 95: ...9 Appendices...
Page 98: ...98 Appendix 2 RC5_4 Drawings Figure 97 Dimensions of RC5_4...
Page 102: ...102 Figure 103 Dimensions of standard OSM mounting kit arrangement for lateral installation...
Page 103: ...103 Figure 104 Dimensions of interface bracket...
Page 104: ...104 Figure 105 Dimensions of OSM mounting kit with M16 pole interface front installation...
Page 105: ...105 Figure 106 Dimensions of OSM mounting kit with M16 pole interface lateral installation...
Page 106: ...106 Figure 107 Dimensions of OSM mounting kit with M20 pole interface front installation...
Page 107: ...107 Figure 108 Dimensions of OSM mounting kit with M20 pole interface lateral installation...
Page 118: ...118 Figure 119 Dimensions of OSM substation mounting kit...
Page 119: ...119 Figure 120 Dimensions of OSM substation mounting kit...
Page 122: ...122 Figure 123 Dimensions of RC mounting kit for through the pole installation...
Page 123: ...123 Figure 124 Dimensions of RC substation mounting kit...
Page 124: ...124 Figure 125 Dimensions of VT mounting kit One VT holder...
Page 132: ...132 Appendix 5 RC5_4 Wiring Diagram Figure 139 RC5_4 wiring diagram...
Page 135: ...135...
Page 136: ......