Ins tallation of the CM: All Models
The installation of the CM is carried out according to the switchgear cubicle design either on the ISM or in
the low voltage compartment of the switchboard. It must in all cases be separated from the high voltage
compartment. The CM shall be installed in an earthed mild steel box with a thickness of not less than 1 mm if it
is attached to the ISM. See Chapter 8 for bolt hole patterns of all CM models.
It is recommended to shield the feeder cables for the CM controls, the CM-signalling and the ISM auxiliary switch
cables (if applicable). If these cables need to be in the high voltage compartment they shall be protected by an
enclosed metal duct.
The CM can operate in any mounting position. Care must be taken for good access and visibility of the terminals,
LEDs and setting elements for operation and maintenance. The ambient conditions as described in the chapter
“Regulations and ambient conditions”(page 64) shall apply.
Figure 50
Draw out type installation
Shielded cable
Secondary circuit plug
Secondary components
Closed steel box > 1 mm
4
5
6
7
Steel plate
> 1 mm thick
ISM
CM
1
2
3
2
5
6
3
7
4
1
3
Figure 51
Fixed type installation
4
2
3
4
1
7
Summary of Contents for ISM15_LD_1 Series
Page 2: ......
Page 6: ...6 1 Introduction 1...
Page 11: ...11 2 Receiving Handling and Storage...
Page 17: ...17 Ins tallation 3...
Page 34: ...34 4 Switching and Control Functions 4...
Page 38: ...38 5 Commiss ioning Operation Maintenance 5...
Page 41: ...41 6 Signalling 6...
Page 45: ...45 6 Product Line 6...
Page 47: ...47 7 Dimens ions and Weights 7...
Page 53: ...53 8 Circuit Diagrams 8...
Page 54: ...54 ISM_LD with CM_16_1 Control Module 8...
Page 55: ...55 8 ISM_LD with CM_1501_01 Control Module...
Page 56: ...56 9 Technical Data 9...
Page 62: ...62 9 9...
Page 63: ...63 10 Regulations and Ambient Conditions 10...
Page 65: ...65 11 Legal Information 11...
Page 69: ...69 11 Date...