![Task Force Tips Ultimatic Instructions For Installation, Operation And Maintenance Download Page 4](http://html2.mh-extra.com/html/task-force-tips/ultimatic/ultimatic_instructions-for-installation-operation-and-maintenance_3699336004.webp)
©Copyright Task Force Tips LLC 2012-2021
4
LIB-065 February 22, 2021 Rev02
3.2 SPECIFICATIONS
Table 3.2
3.3 USE WITH SALT WATER
Use with salt water is permissible provided the equipment is thoroughly cleaned with fresh water after each use. The service life of the
equipment may be shortened due to the effects of corrosion, and is not covered under warranty.
3.4 NOZZLE COUPLINGS
NH (National Hose) threads are standard on all nozzles. Other threads such as NPSH (National Pipe Straight Hose) may be specified at
time of order.
4.0 ELECTRICAL INSTALLATION
For nozzle installation, refer to LIY-500 Remote Control (RC) Monitor Electrical Controls (shipped with TFT monitors or available at
tft.com).
MECHANICAL
Weight
6.4 lbs
2.9 kg
Operating Pressure*
100 psi
7 bar
Maximum Inlet Pressure
800 psi
55 bar
Operating Temperature of Fluid
33 to 120°F
1 to 50°C
Storage Temperature Range
-40 to 150°F
-40 to 65°C
Speed Stream-Fog
3.4 sec.
3.4 sec.
Materials Used
Aluminum 6000 series hard anodized MIL 8625 class 3 type
2, stainless steel 300 series, nylon 6-6, nitrile rubber
*Consult factory for higher pressure applications
ELECTRICAL
Nominal Operating Voltage
12 or 24 VDC (auto sense)
Motor Current
Nominal**
Limit
@ 12 VDC
@ 24 VDC
@ 12 VDC
@ 24 VDC
Nozzle Motor
1 amp
0.5 amps
5 amps
2.5 amps
**with rated pressure applied
Environmental Rating
All components designed to meet minimum rating of IP66/IP67.
CAUTION
Mismatched or damaged waterway connections may cause equipment to leak or uncouple under
pressure. Failure could result in injury. Equipment must be mated to matched connections.
CAUTION
Dissimilar metals coupled together can cause galvanic corrosion that can result in the inability to
uncouple the connection, or complete loss of engagement over time. Failure could cause injury. Per
NFPA 1962, if dissimilar metals are left coupled together, an anti-corrosive lubricant should be
applied to the connection and the coupling should be disconnected and inspected at least
quarterly.
WARNING
This device is not rated as ignition proof, explosion proof, or intrinsically safe. Use only in locations
with adequate ventilation and no hazard of flammable vapor buildup.