5.3.3 ORIFICE PLATE CALIBRATION INFORMATION
In any eductor type system, the accuracy of proportioning depends on the viscosity of the foam concentrate. The orifice plates for the
Master Foam nozzle have been calibrated at 70 degrees F as follows:
Table 5.3.3
6.0 FLOW CHARACTERISTICS
6.1 FIXED FLOW
Pressure on this graph is the nozzle inlet pressure. Losses through piping and monitor must be taken into account to deliver the desired
pressure to the nozzle. Flow on the graph is the water flow entering the nozzle. Any foam educted adds to this flow.
Figure 6.1A
PERCENT
250, 350, 500, and 750 gpm Nozzles
FOAM USED FOR CALIBRATION
0.5% and 1%
Class A foam of 20 centipoise viscosity
3%
3M ATC 3 AR-AFFF product code ATC-603
6%
3M ATC-AFFF product code FC-600F
PERCENT
1000 and 1250 gpm Nozzles
FOAM USED FOR CALIBRATION
1%
Williams Thunderstorm ATC AR-AFFF FC-
601A
3%
Williams Thunderstorm ATC AR-AFFF FC-
601A
PERCENT
1500 and 2000 gpm Nozzles
FOAM USED FOR CALIBRATION
1%
National Universal Gold NFC420
3%
National Universal Gold NFC420
0
50
100
150
200
0
200
400
600
800
1000
1200
175
125
75
25
100
500
700
900
1100
300
1300
5000
0
500
1000
1500
2000
2500
3000
3500
4000
4500
FLOW (gpm)
OPERATING RANGE:
150 psi (10.3 bar)MAXIMUM
50 psi (3.4 bar)MINIMUM
PRESSURE (psi)
BURST PRESSURE
1000 psi (68.9 bar)
FLOW (l/min)
1400
1600
1800
2000
2200
1500
1700
1900
2100
2300
9000
5500
6000
6500
7000
7500
8000
8500
0
5
10
3
7
6
8
9
4
2
1
11
12
13
PRESSURE (bar)
1000 GPM
750 GPM
1250 GPM
500 GPM
350 GPM
250 GPM
1500 GPM
2000 GPM
Table 5.3