Operating Instructions
SIM-KNX
DINRAIL
Release version/date: R1.1 / January 2019
© 2001-2019 TAPKO Technologies GmbH
Im Gewerbepark A15, 93059 Regensburg, Germany
Details, modifications and corrections may be subject to change without notice. TAPKO gives no warranty for the accuracy of the document. All rights reserved.
Product description
Connectors, buttons and LEDs description
The SIM-KNX DINRAIL data servers (with 128 or 254 objects) provide
the possibility of connecting arbitrary end devices having a serial
interface and units that have a microcontroller to KNX TP. In this way,
non-KNX end devices become operable via KNX.
Communication is performed via a simple ASCII protocol. The operating
modes RAW Mode, Interoperability Mode and Transparent Mode are
available. The KNX-certified communication system including all
necessary functions for converting KNX datapoint types is already
contained. Transmission properties can be configured for every group
object separately.
The SIM-KNX DINRAIL is a rail-mounted device for installation in
distribution boards on 35 mm DIN rails. Supplied by the KNX bus line
the device does not require an additional power supply. The serial
interface can be connected with a 9-pin female D-Sub connector. Pin2
is used for sending, Pin3 is used for receiving and Pin 5 is used for
GND. The connection to KNX TP is provided via two screw terminals.
Requirements of Directives EMC, RoHS and LVD are met. Standards for
residential, commercial, and industrial environments are fulfilled. The
full text of the EU declaration of conformity is available at the following
internet address:
RS232 connector
Programming button
KNX TP connection
Programming LED
red:
Programming Mode
active
Rx (received data)
green (blinking):
Telegram traffic
red (blinking):
Transmission error
Tx (transmitted data)
green (blinking):
Telegram traffic
red (blinking):
Transmission error
Technical specifications
Power input
Power supply:
Current consumption:
Housing
Dimensions (HxWxD):
Mounting (IEC60715):
Width in space units:
KNX bus connection:
RS232 connector:
Weight:
Environmental conditions
Operating temperature:
Storage temperature:
Ambient humidity:
21…30 V DC SELV
< 12 mA
90 x 36 x 60 mm
35 mm top-hat rail (TH35)
2 modules at 18 mm
Screw terminals,
0.3-0.5 mm / 0.8 mm
(finely stranded / single core)
9-pin female D-Sub
75 g
-10…50 °C
-25...70 °C
5…93 % (non-condensing)
Electrical safety
Pollution degree (IEC60664):
Protection type (IEC60529):
Protection class (IEC61140):
Overvoltage category (IEC60664):
Approbation (ISO/IEC14543-3):
CE Marking
EU Directives:
Standards:
2
IP20
III
II
KNX-certified
LVD
(2014/35/EU)
EMC (2014/30/EU)
RoHS (2011/65/EU)
EN50491-5-1
EN50491-5-2
EN50491-5-3
EN50581
EN60950-1
Mounting, commissioning and safety notes
Installation and maintenance
After connection to the KNX bus system, the device works with its
default settings as intended
Warning
: Do not connect to 230 V. The device is supplied by the
KNX bus and does not require any additional external power supply
The device may only be installed and put into operation by a
qualified electrician or authorized personnel
For planning and construction of electric installations the appropriate
specifications, guidelines and regulations in force of the respective
country have to be complied
For mounting use an appropriate equipment according to IEC60715
Installation on a 35 mm DIN rail (TH35)
Connect the KNX bus line as for common KNX bus connections with a
KNX bus cable, to be stripped and plugged into a KNX TP connector
Do not damage electrical insulations during connecting
Installation only in dry locations
Accessibility of the device for operation and visual inspection must be
provided
For changing settings use the ETS
The housing must not be opened
Protect the device from moisture, dirt and damage
The device needs no maintenance
If necessary, the device can be cleaned with a dry cloth
In the case of damage (at storage, transport) no repairs may be
carried out by unauthorized personnel