Product description
Connectors, buttons and LEDs description
The KNX TP line coupler MECtp connects two TP lines as main line and
subline. MECtp can be used as KNX line coupler and KNX area coupler
or KNX repeater (without filtering). The lines have a galvanic separation
between each other. Operational and filtering states, malfunction and
faulty communication are indicated by LEDs.
MECtp is able to filter the traffic according to the installation place in
the bus system hierarchy and according to the built-in filter tables for
group oriented communication. Extended frames and long messages
with up to 240 bytes APDU length are supported. For commissioning
and troubleshooting a configurable Manual Function to temporarily
deactivate filtering is available. It can be activated by a single button
press and its switch-off after a pre-set time period is automatic
Suppress device configuration from the subline
Enable/disable filtering of Group telegrams or Physical telegrams
Number of repetitions is reducible
Confirmations can be added to sent out telegrams
Requirements of Directives EMC, RoHS and LVD are met. Standards for
residential, commercial, and industrial environments are fulfilled. The
full text of the EU declaration of conformity is available at the following
internet address:
Bus state KNX TP (Main line)
green:
Main line OK
orange:
Manual Function active
Bus state KNX TP (Subline)
green:
Subline OK
Telegram traffic KNX TP (Main line)
green (blinking):
Telegram traffic extent
red (blinking):
Transmission error
Telegram traffic KNX TP (Subline)
green (blinking):
Telegram traffic extent
red (blinking):
Transmission error
Group Address routing
green:
Filter active
orange:
Route all
red:
Block all
<off>:
Main line / subline different
Function button
Physical Address routing
green:
Filter active
orange:
Route all
red:
Block all
<off>:
Main line / subline different
Programming button
KNX TP main line connector
Programming LED
red:
Programming Mode active
KNX TP subline connector
Technical specifications
Power input
Power supply:
Current consumption:
Housing
Dimensions (HxWxD):
Mounting (IEC60715):
Width in space units:
KNX bus connections:
Weight:
Environmental conditions
Operating temperature:
Storage temperature:
Ambient humidity:
21…30 V DC SELV
< 10 mA
(from main line)
90 x 36 x 71 mm
35 mm top-hat rail (TH35)
2 modules at 18 mm
KNX connector (red/black)
for KNX TP main line & subline
62 g
-5…45 °C
-20...60 °C
5…93 % (non-condensing)
Electrical safety
Pollution degree (IEC60664):
Protection type (IEC60529):
Protection class (IEC61140):
Overvoltage category (IEC60664):
Approbation (ISO/IEC14543-3):
CE Marking
EU Directives:
Standards:
2
IP20
III
III
KNX-certified
LVD
(2014/35/EU)
EMC (2014/30/EU)
RoHS (2011/65/EU)
EN50491-5-1
EN50491-5-2
EN50491-5-3
EN50581
EN61000-6-2
EN61000-6-3
Mounting, commissioning and safety notes
Installation and maintenance
After connection to the KNX bus system, the device works with its
default settings as intended
Warning
: Do not connect to 230 V. The device is supplied by the
KNX bus and does not require any additional external power supply
The device may only be installed and put into operation by a
qualified electrician or authorized personnel
For planning and construction of electric installations the appropriate
specifications, guidelines and regulations in force of the respective
country have to be complied
For mounting use an appropriate equipment according to IEC60715
Installation on a 35 mm DIN rail (TH35)
Connect the KNX bus line as for common KNX bus connections with a
KNX bus cable, to be stripped and plugged into a KNX TP connector
Do not damage electrical insulations during connecting
Installation only in dry locations
Accessibility of the device for operation and visual inspection must be
provided
For changing the configuration use the ETS
The housing must not be opened
Protect the device from moisture, dirt and damage
The device needs no maintenance
If necessary, the device can be cleaned with a dry cloth
In the case of damage (at storage, transport) no repairs may be
carried out by unauthorized personnel
Configuration details and ETS database:
1
2
3
4
5
A
6
B
C
7
D