KT-24534
Proprietary and Confidential
05/29/2012
Tantalus Utility Network™
The TC-11/1210 and TC-11/1210-RD are two-way 900 MHz LAN smart meter communication modules that are
integrated into the GE I-210 ® and I-210+ ® family of electrical watthour meters. The GE I-210 metrology unit
sends digital pulses to the communication module that represents the energy delivered or received to/from the
service. The GE I-210+ metrology unit has 2-way communication to the Tantalus smart communication using the
ANSI C12.18 protocol to convey energy consumption and it also allows the communication module to activate the
service disconnect switch where applicable. The Tantalus LAN communication module delivers meter readings on
request or on a programmed schedule for Time-of-Use and interval data applications. The LAN communication
module also reports power outages and monitors power quality including voltage (plus sag/swell alarms) and
momentary outages (blinks).
Warning
Energized meters, meter sockets and distribution lines present the risk of
electrical shock. All work on this equipment should be performed by qualified
metering specialists or industrial electricians.
Personnel working with this equipment should follow all utility company
established operation and safety procedures.
Installation Instructions
1.
Remove the existing meter from the meter socket and record the final reading per utility standard practice.
2.
Inspect the meter socket jaws to ensure that they are in good condition.
3.
Perform voltage checks, line-to-line and line-to-neutral, to ensure the voltage is at proper levels.
4.
Visually inspect the meter. Ensure that the optical interface is secured in place on the meter base.
5.
Install the meter and observe the Network Status LED to verify that a valid association candidate is found per
the table on the reverse page.
6.
Install the meter ring and seal.
7.
Record the new meter number and initial reading per utility standard practice.