HIGH VOLTAGE SAFETY 

It is essential to follow safe working procedures when working with high voltage.  Information on 
accepted  codes  of  practice  should  be  obtained  from  your  local  health  and  safety  regulatory 
body. 

It  is  essential  that  the  KV50-20D  MK2  is  only  used  in  a  suitable  test  environment.  
EN50191:2001 (Erection and Operation of Electrical Test Equipment) provides information on 
the installation and use of test installations and is referenced by health and safety law in the EU.  
EN50191:2001 is available from T&R Test Equipment. 

IEEE standard 510-1983 (IEEE Recommended Practices for Safety in High-Voltage and High-
Power Testing) also provides a working framework for establishing safe procedures but must 
be read in conjunction with local regulations and accepted codes of practice. 

The following excerpts are taken from IEEE 510 

  All  ungrounded  terminals  of  the  test  equipment  or  apparatus  under  test  should  be 

considered as energised. 

  Common ground connections should be solidly connected to both the test set and the test 

specimen.  As  a  minimum,  the  current  capacity  of  the  ground  leads  should  exceed  that 
necessary to carry the maximum possible ground current. The effect of ground potential rise 
due to the resistance and reactance of the earth connection should be considered. 

  Precautions should be taken to prevent accidental contact of live terminals by personnel, 

either by shielding the live terminals or by providing barriers around the area. 

  The circuit should include instrumentation for indicating the test voltages. 

  Appropriate  switching  and,  where  appropriate,  an  observer  should  be  provided  for  the 

immediate  de-energisation  of  test  circuits  for  safety  purposes.  In  the  case  of  dc  tests, 
provisions  for  discharging  and  grounding  charged  terminals  and  supporting  insulation 
should also be included. 

  In the use of signal-gathering equipment, each device should be used in such a manner that 

it  will  not  present  a  personnel  hazard  should  it  inadvertently  become  a  part  of  the  high-
voltage circuit or fail to function properly. 

  High-voltage  and  high-power  tests  should  be  performed  and  supervised  by  qualified 

personnel.  

  Consideration  should  be  given  to  safety  regulations  which  may  apply  to  specific 

circumstances; for example, HSE, company, or government regulations. 

 

Summary of Contents for KV50-20D mk2

Page 1: ...roduct High Voltage AC Test Set Type KV50 20D mk2 DESIGNED AND MANUFACTURED BY T R Test Equipment Limited 15 16 Woodbridge Meadows Guildford Surrey GU1 1BJ United Kingdom Telephone 01483 207428 e mail...

Page 2: ...ol unit and HV transformer that must be connected to a local earth Ensure that the unit is properly grounded before making any connections to inputs or outputs Terminal ratings must be observed to pre...

Page 3: ...men As a minimum the current capacity of the ground leads should exceed that necessary to carry the maximum possible ground current The effect of ground potential rise due to the resistance and reacta...

Page 4: ...The following safety symbols appear in this manual CAUTION This action or procedure may be dangerous if not carried out correctly and may cause damage to the equipment or connected equipment WARNING T...

Page 5: ...unctions 8 2 OPERATION 10 2 1 Safety 10 2 2 Installation 10 2 2 1 Test area 10 2 2 2 Mains supply 10 2 2 3 Earthing 10 2 2 4 Interlock beacon circuit connections 13 2 2 5 Grounding of the high voltage...

Page 6: ...Output current Continuous 5 min on 15 min off KV50 20D MK2 0 50kV 12mA 20mA One side of the high voltage transformer output is connected to the earth system of the equipment 1 1 3 Zero voltage interlo...

Page 7: ...t the output current on short circuit 1 1 6 Metering The equipment is fitted with a two range kV meter that indicates the output voltage It is also fitted with a mA meter that meters the output curren...

Page 8: ...ltage control D HV transformer connector L Output trip level control E Primary trip circuit breaker M N HV output on off switches illuminated green when output is off illuminated red when output is on...

Page 9: ...9 Figure 1 2 HV transformer connections T HV output connection V Control unit connector U Earth terminal for connection to low impedance local earth This terminal MUST be connected as specified...

Page 10: ...supply or HV unit interlock to ensure that the unit cannot be switched on unless the area is secure Refer to EN50191 2001 for further details of suitable test areas The test area must also be identif...

Page 11: ...11 Figure 2 1 KV50 20D MK2 leads...

Page 12: ...12 Figure 2 2 Earthing in metal test cage Figure 2 3 Earthing in temporary test area without earthed enclosure...

Page 13: ...nterlock circuit remove the shorting link from the plug supplied and wire the external interlock circuit in its place The interlock circuit has a self checking circuit and will sound an audible alarm...

Page 14: ...6 1 High voltage output clearances Adequate clearances must be maintained between the following parts and any other conducting object whether earthed or not HV output connection and all parts connecte...

Page 15: ...ding frame Connect control unit earth terminal to earth clamp using supplied earth lead Connect the following leads to the HV transformer earth terminal Earth lead to earth clamp Earth stick Hang eart...

Page 16: ...The key is only removable in the OFF position The key is trapped in the ON position Remove the earth stick from the HV connection of the transformer and leave the test cage Place the earth stick by t...

Page 17: ...mp will extinguish and the HV ON lamp will be lit The output voltage can now be increased to the desired level as indicated on the kV meter In the event of a test object failure the HV output will be...

Page 18: ...control unit is the regulator brush This should be inspected for damage and wear when the unit is re calibrated 3 1 Removal of control unit from case a Remove the lid from the control unit and rest it...

Page 19: ...ovided with the equipment Replacement part number a Mains input lead S000 0580 b Interlock plug GX134 0005 c 2 x 5m earthing leads for control and HV units AX138 0002 d Earth clamp AX138 0003 e Interc...

Page 20: ...frame Accuracy of instruments kV meter 5 of reading 5d mA meter 2 of reading 5d H V Transformer 2 5kV RMS for 1 minute between primary and earth 2 5kV RMS for 1 minute between earthy end of secondary...

Page 21: ...21...

Page 22: ......

Page 23: ...23 6 REVISION Product Type High Voltage AC Test Set KV50 20D mk2 File OM0041 1 docx Author M Clancy Issue Date 1 13 09 2022 Checked By G Bond Date 07 12 22...

Page 24: ...24 Drawings required A2 002227 latest issue KV50 20D mk2...