3 Addressable  Sounder  Circuit  Module Unit Configuration  

 

3.1 Preparation     

The TX7930 handheld programmer is used to configure

 

Addressable Sounder Circuit Module Unit soft 

address and parameter. This tools are not included, must be purchased separately. The programmer 
is packed  with twin 1.5V AA  battery and cable, ready  for usage once received.  

It is mandatory for the commissioning personnel to  have programmer tool in order to adjust the 

Unit

 

conferring to the site situation and environmental requirements.   

Program a unique address number for each device according to the project layout before placing 
from the Terminal Base.  

Warning: Disconnect the  loop connection whilst connecting to the handheld programmer.  

3.2 Write: Addressing       

1.

 

Connect the programming cable to Z1 and Z2 terminals (Figure 3). Press “Power” to switch on 

the unit. 

2.

 

Switch-on the programmer, then press button “Write”  or number “2”  to enter Write  Address 

mode (Figure 4). 

3.

 

Input the desire device address value from 1 to 254, and then press “Write” to save the new 

address (Figure 5). 

 

Note:

  

If display “Success”,  means the entered address is confirmed.  If display  “Fail”, means 

failure to program the address (Figure 6). 

4.

 

Press “Exit” key to go back Main Menu.  Press “Power”  key

 

to switch-off the programmer. 

 

 

 

Terminal Description  

Z1 Signal In Non-polarity 

Z2 Signal In Non-polarity 

D1 External Power Supply In   Non-

polarity 

D2 External Power Supply In   Non-

polarity 

L+  Remote Indicator (+) 

L-   Remote Indicator (-) 

 

 

 

 

 

Figure 2: Wiring  

 

Summary of Contents for TX7211

Page 1: ...TX7211 Addressable Sounder Circuit Module Installationand Operation Manual TANDA UK Technology Copyright 2015 All right reserved...

Page 2: ...efore installing the module to ensure proper and safe operation of the system European Union directive 2012 19 EU WEEE directive Products marked with this symbol cannot be disposed of as unsorted muni...

Page 3: ...Content 1 Introduction 4 1 1 Overview 4 1 2 Feature and Benefits 4 1 3 Technical Specification 4 2 Installation 5 2 1 Installation Preparation 5 2 2 Installation and Wiring 5 3 Addressable Sounder Ci...

Page 4: ...ore convenient to the installer The unit is compatible to the TX7004 Analogue Intelligent Fire Alarm Control Panel produced by single manufacture Tand to avoid addressable communication compatibility...

Page 5: ...al to consider the requirement of both sides of the Unit to avoid malfunction and typical fault scenario The main caution is to ensure that the voltage rating of the equipment and Unit are compatible...

Page 6: ...device according to the project layout before placing from the Terminal Base Warning Disconnect the loop connection whilst connecting to the handheld programmer 3 2 Write Addressing 1 Connect the pro...

Page 7: ...mode I II III IV can be set in field referring to the corresponding parameters 1 2 3 4 Program the module before installation use proper mode according to the field conditions Mode Address Quantity O...

Page 8: ...s an example the connection is shown in Fig 9 Fig 9 4 General Maintenance 1 Inform the suitable personnel before conducting the maintenance 2 Disable Addressable Zone Monitor Unit on the control panel...

Page 9: ...to keep the Addressable Sounder Circuit Module Unit working in good condition please maintain the equipment continuously according to recommendations from manufacturers and relative nation codes and l...

Reviews: