Taico TK4800 User Manual Download Page 14

14

7. Maintenance Precautions

In the later stage of installation and use, the iron lithium battery can be simply maintained

and inspected, because of its maintenance-free characteristics, the maintenance period

can be extended, such as once every 3 months.

Check whether the pole column and connection lines of LiFePO4 battery are

loosed, damaged, deformed or corroded, and whether the battery case is

damaged or deformed;

Observe the state of the battery pack running indicator light, normal state is green

light, battery pack CAPCITY light only the last flicker, indicating that the battery

power is low, the battery is about to dry off the output;

When there is a failure, the battery pack flashes ALM the red light and sends out

an alarm. Please check whether the battery connection is correct or over-current;

then press the RST reset key to see if the failure is eliminated after the battery

restarts. If it can not be eliminated, please contact the manufacturer to handle, do

not open the battery case;

For a multi-battery parallel application scenario, if one of the battery fails and

needs to be replaced, make sure that the voltage difference between the newly

replaced battery and the other batteries to be parallel is within 2V, if the Voltage

difference is large, High voltage battery pack charge low voltage battery pack

large current, low voltage battery pack charge over-current protection, resulting in

unable to charge;

Record the time and number of power outages, the battery power supply time to
do detailed statistics;

8. FAQ Analysis and Solutions

8.1 Undervoltage alarm

ALM indicator lights flicker, RUN operation indicator lights out.

Cause analysis:

(1) The load current is too large that exceeds the battery’s discharge

Summary of Contents for TK4800

Page 1: ...1 TK4800 51 2V 100Ah Lithium Iron Phosphate Battery User Manual...

Page 2: ...imensions 5 4 2 Battery Parameters 5 4 3 Interface Definitions 6 5 LiFePO4 Battery Safety Operating Guidelines 9 5 1 Application Schematic 9 5 2 Tools 9 5 3 Security equipment 9 6 Installation 10 6 1...

Page 3: ...e battery charge percentage shall not be less than 70 5 If the battery is fully discharged it should be charged within 12 hours 6 Before maintenance batteries and equipment must be cut off firstly 7 D...

Page 4: ...it for connecting this battery with any faulty or incompatible devices 1 2 4 When fire occurs only dry powder fire extinguishers can be used liquid fire extinguishers are prohibited 1 2 5 Do not disas...

Page 5: ...ation can balance the battery module each single string core Expansion flexible configuration multiple battery modules can be parallel expansion capacity applicable to different standby time requireme...

Page 6: ...482 400 177 Weight About 45KG Working voltage 43 2 58 4V Charging voltage 56 8 58 4V Charging current limiting 10A The default charging current is greater than 55A and the current limiting is on Stan...

Page 7: ...LED indicator lights up for 0 5 seconds from the lowest power lamp When the BMS is activated press reset button for 6 seconds and release the protection board is reset and the LED lights are lit for...

Page 8: ...8 4 3 2 RS485 2 With a dual RS485 interface the default baud rate is bps 9600 can be expanded in parallel battery pack communication interconnection 4 3 3 RS232 Default baud rate bps 9600...

Page 9: ...ial switch position 1 2 3 4 0 OFF OFF OFF OFF 1 ON OFF OFF OFF 2 OFF ON OFF OFF 3 ON ON OFF OFF 4 OFF OFF ON OFF 5 ON OFF ON OFF 6 OFF ON ON OFF 7 ON ON ON OFF 8 OFF OFF OFF ON 9 ON OFF OFF ON 10 OFF...

Page 10: ...rrent protection Elimin ation Elimin ation Elimina tion Elimina tion Elimin ation Elimi natio n Stop discharge Temperature overcurrent short circuit reverse connection failure protection Elimin ation...

Page 11: ...idelines 5 1 Application Schematic 5 2 Tools The following tools are needed to install batteries Use insulated tools to prevent accidental electric shock or short circuit If there is no insulation too...

Page 12: ...etween 0 c and 50 C the temperature and humidity remain constant 6 1 5 This area has little dust and dirt Attention If the ambient temperature is out of working range the battery pack will stops to wo...

Page 13: ...own below Note When the battery is placed or pulled out of the rack beware of the battery slipping out Note when connecting the equipment the battery output positive and negative electrodes should be...

Page 14: ...tery connection is correct or over current then press the RST reset key to see if the failure is eliminated after the battery restarts If it can not be eliminated please contact the manufacturer to ha...

Page 15: ...be activated at the charging input end 8 3 Temperature Protection ALM alarm indicator lights flicker RUN operation indicator lights out Cause analysis Ambient temperature may be too high or too low So...