2-6
Hardware Installation Procedure
Coral IPx Office Installation Manual
Si
te Inspection
2
00
General Requirements
The Coral IPx Office operates from a standard wide input of 100 to 240VAC, 47 to
63Hz source or from a –40 to –56VDC source.
1.
Verify that electrical service is sufficient and located in close proximity to the
system. Coral IPx Office system requires at least one dedicated branch circuit
with at least two receptacles: one for the cage, and one for ancillary equipment
such as data terminals or personal computers, external paging equipment, or
test instruments, etc.
2.
For 115VAC or 230VAC power, a 1.85mm
2
or 14AWG wire must be used in
the circuit branch.
3.
Each branch circuit must be independently protected by a fuse or circuit
breaker, and must not be controlled by a switch. C-type fuses must be used
where required by local authorities.
4.
The receptacle for the Coral system branch circuit must be located within
4 feet (1.2m) of the cage for AC operated systems, or within 4 feet (1.2m) of
the 48VDC power supply for DC operated systems.
5.
Auxiliary branch circuit receptacles should be located conveniently for
ancillary equipment, and should allow data terminals, personal computers, or
test instruments to be operated near the system.
6.
lists the voltages and current requirements for each cabinet.
DC Electrical Requirements
DC powered units must comply with the following instructions:
1. Restricted Access Area
: The DC powered equipment should only be installed
in a Restricted Access Area.
2. Installation Codes
: The equipment must be installed according to country
national electrical codes. For North America, equipment must be installed in
accordance with the US National Electrical Code, Articles 110-16, 110-17 and
110-18 and the Canadian Electrical Code, Section 12.
3. Overcurrent Protection
: A readily accessible listed branch circuit overcurrent
protective device rated "30A/60VDC minimum slow blow" must be
incorporated in the building wiring for every three units.
...................................................................................................
3
Electrical Requirements
Summary of Contents for Coral IPx Office
Page 2: ......
Page 4: ......
Page 25: ...xxi Figure 11 10 WiFi Antenna Removal 11 18...
Page 26: ......
Page 28: ......
Page 36: ...1 8 Introduction Coral IPx Office Installation Manual About this Manual 1 NOTES...
Page 44: ......
Page 96: ......
Page 106: ...3 10 Initial Power up Tests Coral IPx Office Installation Manual Common Control Test 3 NOTES...
Page 122: ......
Page 138: ......
Page 182: ......
Page 234: ......
Page 258: ...7 24 Power Supply Coral IPx Office Installation Manual PS Office DC Power Supply Unit 7 NOTES...
Page 260: ......
Page 302: ...8 42 Common Control Cards Coral IPx Office Installation Manual Compact Flash Disk 8 NOTES...
Page 310: ...8 50 Common Control Cards Coral IPx Office Installation Manual DBM Card 8 NOTES...
Page 312: ......
Page 372: ...9 60 Shared Service Cards Coral IPx Office Installation Manual VoIP Media Gateway MG 9 NOTES...
Page 420: ......
Page 488: ......
Page 509: ......