iWorx® VPU2
505-010-2, Effective: April 29, 2014
21
© 2014 Taco Electronic Solutions, Inc.
When the
Temperature Differential Maximum
is set to 0, the
Supply Temperature Setpoint Reset Curve
is disabled and
the VPU2 operates with the usual heating and cooling supply air temperature setpoints.
Figure 7: Supply Temp Reset Curves
Outside Air Temperature Lockouts
Heating can be disabled during warm weather by setting the outdoor air temperature heating lockout
Max OAT Heat
. If
the OAT is above the heating lockout temperature, the primary heating mode is disabled and the controller can only be
in the primary off or primary cooling modes. This feature requires a controller that broadcasts the OAT, such as an
ASM2 be installed on the network.
Cooling can be disabled during cold weather by setting the outdoor air temperature cooling lockout
Min OAT Cool
. If
the OAT is below the cooling lockout temperature, the primary cooling mode is disabled and the controller can only be
in the primary off or primary heating modes. This feature requires a controller that broadcasts the OAT, such as an
ASM2 be installed on the network.