background image

APPLICATION:

The Taco 1400 Series Hi-Capacity circulators are designed
for use on a wide range of hydronic heating, cooling or
domestic water re-circulating systems. Features include a
quiet running, close-coupled, thermally protected motor
assembly with permanent split-capacitor and permanently
lubricated bearings. A stainless steel face plate and
mechanical seal with a non-ferrous impeller make the 1400
series an ideal choice for years of maintenance-free oper-
ation on open or closed systems.

Note: Always use Bronze body circulators on open,
fresh water systems.

OPERATING SPECIFICATIONS:

Maximum Working Pressure:

150 psi (1000 kPa)

Maximum Operating Temperature:

225ºF (107ºC)

Electrical Rating:

115V/60Hz/1Ph or 230V/60Hz/1Ph

REMOVAL OF EXISTING PUMP FROM SYSTEM PIPING:

1. Disconnect and lock-out electrical supply to pump.

2. Close isolation valves on suction and discharge sides

of pump. If valves are not installed, the system may
need to be drained.

3. Remove capacitor box cover and disconnect electrical

supply lines to pump.

4. Loosen flange bolts and shift pump body slightly to

relieve any remaining system pressure. 

5. Remove flange nuts/bolts and pump from system. 

INSTALLATION OF “1400 SERIES” CIRCULATOR:

A. Location:

• Install pump with sufficient room for future inspection,

maintenance and service.

• It is recommended that isolation valves be installed on

the pump suction and discharge to simplify future ser-
vice or replacement without draining the system.

1. Using teflon tape or high quality thread sealant, install

Taco companion flanges on threaded pipe ends to
ensure proper fit-up and leak protection.

Instruction Sheet

1400 Series Hi-Capacity Circulator

102-147

SUPERSEDES: June 1, 2003 

EFFECTIVE: August 15, 2005

Plant ID# 001-1183

INSTALLER: Please leave these instructions for 

owner’s use.

CAUTION: Taco “1400 Series” circulators are
designed for indoor use only.

CAUTION: Taco circulators are designed to
operate with water and most glycol solutions.
The addition of certain chemical additives
may cause early failure and void warranty.

CAUTION: This pump has a mechanical seal
which, by design, will eventually wear and
leak. Allow access for periodic inspection
and leak detection. Provide adequate
drainage to prevent property damage.

CAUTION: To prevent injury, allow system
water to cool to 100ºF before removing old
pump or draining system. Leave drain valve
open until service/replacement is complete.

1400 SERIES COMPANION FLANGE SETS

Models Connection

3

4

"

1

"

1

1

4

"

1

1

2

"

2"

1400-10/10B

1400-20/20B

1400-50/50B

1400-30/30B

1400-40/40B

1400-60/60B

1400-70/70B

Iron NPT

Bronze NPT

Bronze Sweat

Shut-Off NPT

Shut-Off Sweat

Iron NPT

Bronze NPT

Iron NPT

Bronze NPT

110-251F

110-251BF

110-523BSF

243-1

243-2

110-252F

110-252BF

110-524BSF

244-1

244-2

110-253F

110-253BF

110-525BSF

245-1

245-2

194-1540F

194-1540BF

110-254F

110-254BF

110-526BSF

246-1

194-1542F

194-1542BF

185-086C

185-086B

Summary of Contents for 1400 Series

Page 1: ...e installed on the pump suction and discharge to simplify future ser vice or replacement without draining the system 1 Using teflon tape or high quality thread sealant install Taco companion flanges on threaded pipe ends to ensure proper fit up and leak protection Instruction Sheet 1400 Series Hi Capacity Circulator 102 147 SUPERSEDES June 1 2003 EFFECTIVE August 15 2005 Plant ID 001 1183 INSTALLE...

Page 2: ...ccordance with local and national codes and regulations Electrical supply and grounding wires must be suitable for at least 90ºC 194ºF 1400 Series circulators are thermally protected and do not require external overload protection 1 Be sure all electrical power to pump is disconnected and locked out before proceeding with wiring 2 Loosen capacitor conduit box screw and remove cover 3 Attach approp...

Page 3: ...ce the face plate to its original posi tion Carefully tap the face plate evenly into the recess in the motor housing 7 Clean the impeller shaft before installing the new seal 8 Lubricate the impeller shaft with soapy water Do not install new seal on a dry impeller shaft or damage to seal may result 9 Slide the new carbon seal and spring assembly onto the shaft until it contacts the ceramic seal se...

Page 4: ... been subject to misuse misapplication the addition of petroleum based fluids or certain chemical additives to the systems or other abuse will not be covered by this warranty If in doubt as to whether a particular substance is suitable for use with a Taco product or part or for any application restrictions consult the applicable Taco instruction sheets or contact Taco at 401 942 8000 Taco reserves...

Reviews: