DESCRIPTION:

The 0034ePlus is a high performance, variable speed, high-efficiency, wet-rotor 

circulator with an ECM, permanent magnet motor and an advanced digital LED 

display controller for easy programming and diagnostic feedback. With 5 operating 

modes and simple keypad programming, its variable speed performance curves are 

equivalent to the Taco 009, 0010, 0011, 0012, 0012 3-Speed, 0013, 0013 3-Speed & 

0014. Ideal for large residential and light commercial hydronic heating, chilled water 

cooling and domestic hot water systems. The 0034ePlus reduces power consumption 

by up to 85% compared to equivalent AC permanent split capacitor circulators.

APPLICATION:

•  Maximum operating pressure: 150 psi (10.3 bar)

•   Minimum NPSHR: 18 psi at 203˚F (95˚C)

•   Maximum fluid temperature: 230°F (110˚C)

•   Minimum fluid temperature: 14°F (-10˚C)

•   Electrical specifications:

   

Voltage: 115/208/230V, 50/60 Hz, single phase

   

Maximum operating power: 170W

   

Maximum amp rating: 1.48 (115V) / .70 (230V)

•   Equipped with a cast iron or stainless steel casing

•   SS Model suitable for open loop potable water systems

•   Taco circulator pumps are for indoor use only – employer uniquement a l’interieur

•   Acceptable for use with water or maximum of 50% water/glycol solution

FEATURES:

•  Simple keypad programming

•  Digital LED screen display (Watts, GPM, Head, RPM and diagnostic error codes)

•  Five operating modes to match any system requirements - activeADAPT,  

 

 

 

 

 

  Constant Pressure, Proportional Pressure, Variable Fixed Speed or 0-10V DC input

•   Replaces all single speed and 3-speed circulators in its class

•   ECM performance equivalent to Taco’s 009, 0010, 0011, 0012, 0013 & 0014 circulators

•   Multi-color LED display showing power on, mode setting and error code diagnostics

•   Use with a Taco ZVC Zone Valve Control or SR Switching Relay for ON/OFF operation

•   Nut-capture feature on flanges for easier fit up

•   Dual electrical knockouts and removable quick-connect terminal strip for easy wiring

•   Double insulated

•   Whisper quiet operation

•  

BIO Barrier®

 protects the pump from system contaminants

•  

SureStart®

 automatic unblocking and air purging mode

•   Rotatable control cover to allow any pump body orientation 

INSTALLATION:

WARNING: Do not use in swimming pool or spa areas. Pump has not been investigated for these applications.

AVERTISSEMENT : Ne pas utiliser dans une piscine ou un spa. La pompe n’a pas été étudiée pour ces applications.
CAUTION: The addition of petroleum based fluids or certain chemical additives to systems using TACO equipment

voids the warranty. Consult factory for fluid compatibility.
ATTENTION : L’ajout de liquides à base de pétrole ou de certains additifs chimiques à des systèmes utilisant un

équipement TACO annule la garantie. Consultez le fabricant pour connaître la compatibilité de liquides.
CAUTION: Installations at elevations over 5000 feet must have higher fill pressure of 20 psi minimum to prevent

pump cavitation and flashing. Premature failure may result. Adjust expansion tank pressure to equal fill pressure. 

A larger size expansion tank may be required.
ATTENTION : Des installations à des altitudes de plus de 1600 mètres doivent présenter une pression de remplissage plus élevée de 20 psi 

au minimum afin d’éviter toute cavitation ou flashing de la pompe. Une défaillance prématurée peut en résulter. Réglez la pression 

du réservoir d’expansion de façon qu’elle soit égale à la pression de remplissage. Un réservoir d’expansion d’une taille supérieure 

peut être nécessaire.

Instruction Sheet

ECM

 

High-Efficiency Circulator with Digital Display Controller

102-544

SUPERSEDES: NEW 

EFFECTIVE: December 2, 2019

Plant ID No. 001-5021

-1-

Certified to

NSF/ANSI 61 & 372

Figure 1

Cast Iron model: 0034ePlus-F2
Stainless Steel model: 0034ePlus-SF2

Summary of Contents for 0034ePlus

Page 1: ...witching Relay for ON OFF operation Nut capture feature on flanges for easier fit up Dual electrical knockouts and removable quick connect terminal strip for easy wiring Double insulated Whisper quiet operation BIO Barrier protects the pump from system contaminants SureStart automatic unblocking and air purging mode Rotatable control cover to allow any pump body orientation INSTALLATION WARNING Do...

Page 2: ...ZONE 3 ZONE 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 FC FC FC FC FC FC FC FC FC ZONE 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 FC FC Optional Location FC FC ZONE 1 ZONE 2 ZONE 3 FC FC Optional Location FC FC Figure 2 PREFERRED PIPING FOR CIRCULATORS ON BOILER SUPPLY PREFERRED PIPING FOR CIRCULATORS ON BOILER RETURN PREFERRED PRIMARY SECONDARY PIPING FOR CIRCULATORS ON BOILER SUPPLY ...

Page 3: ... PRIMARY SECONDARY PIPING FOR ZONE VALVES ON BOILER SUPPLY ALTERNATE PIPING FOR ZONE VALVES ON BOILER RETURN igure 3 MOD CON BOILER ZONE 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 Figure 3 PREFERRED PIPING FOR ZONE VALVES ON BOILER SUPPLY ALTERNATE PIPING FOR ZONE VALVES ON BOILER RETURN PREFERRED PRIMARY SECONDARY PIPING FOR ZONE VALVES ON BOILER SUPPLY ...

Page 4: ... system will result in immediate lubrication of the bearings It is always good practice to flush a new system of foreign matter before starting the circulator WARNING Risk of electric shock To reduce the risk of electric shock be certain that it is connected only to a properly grounded grounding type receptacle Follow all local electrical and plumbing codes AVERTISSEMENT Risque de choc électrique ...

Page 5: ... être identiques aux pièces remplacées 4 Wiringthecirculator Disconnect AC power supply Remove terminal box cover Attach a wiring connector into knockout hole Use flexible conduit only The green terminal plug may be removed to simplify wiring then snapped back in place Connect Line Hot power to the L terminal Neutral to the N terminal and Ground to the G terminal See wiring diagram above The 0034e...

Page 6: ... 0 10V DC Analog external input or PWM pulse width modulation input from building control system variable speed Yellow LED Figure 7 Digital Display Operating Modes 8888 8888 8888 Orange LED C Purple LED activeADAPT 0 10V Green LED P Blue LED min max Yellow LED activeADAPT 0 10V activeADAPT 0 10V activeADAPT 0 10V LED FUNCTION SETTING activeADAPT Constant Pressure C1 C2 C3 C4 C5 Proportional Pressu...

Page 7: ...35 40 45 50 55 Flow Rate Q GPM 0 5 10 15 20 25 30 35 Head ft 0034ePlus High Efficiency Circulator activeADAPT Range activeADAPT activeADAPT Mode activeADAPT is an operating mode designed for constant circulation systems On this setting the circulator will sense changes in system flow and head conditions and adjust the operating curve automatically See activeADAPT operating range in the chart to th...

Page 8: ...ional Pressure Curves Power Consumption 5 0 10 15 20 25 30 35 40 45 50 55 Flow Rate Q GPM 0 5 10 15 20 25 30 35 Head ft P1 8 2 ft P2 14 6 ft P3 20 8 ft P4 24 8 ft P5 28 6 ft 0034ePlus High Efficiency Circulator Proportional Pressure Curves Proportional Pressure Mode Circulator will vary speed to maintain desired feet of head proportional pressure curve There are 5 setting options 8 2 28 6 ft ...

Page 9: ...y Circulator Variable Fixed Speed Range Power Consumption MAX 100 1 MIN 5 0 10 15 20 25 30 35 40 45 50 55 Flow Rate Q GPM 0 5 10 15 20 25 30 35 Head ft MAX 100 1 Head 34 ft Head 1 ft MIN 0034ePlus High Efficiency Circulator Variable Fixed Speed Range Fixed Speed Mode Variable fixed speed operation Setting from 1 100 speed ...

Page 10: ... plug Figure 8 Ref 4 from the electronic board Figure 8 Ref 5 4 Insert the cable Figure 8 Ref 6 in the cable strain relief gland M12x1 5 Figure 8 Ref 7 provided in carton and screw it to the cover 5 Strip Minimum 25 the ends of the wires insert them into the connector as shown Figure 8 Ref 4 and fix them with screws Figure 8 Ref 8 6 Re connect the terminal plug to the electronic board replace the ...

Page 11: ...ow Rate Q GPM 0034ePlus High Efficiency Circulator 0 10V DC Performance Curves 100 75 50 25 0 0 10V 4V 2V 8V 6V 10V 11 0 V Circulator off not powered 2 V Circulator powered in standby 5 V Circulator on and running 8 V Warning presence overheating air 10 V Alarm presence Circulator blocked under voltage over temperature E1 Pump locked Loss of step Stop E2 Under Voltage Stop E3 Overheating Warning I...

Page 12: ...r impeller rotation 7 If the circulator still doesn t run it will need to be replaced FAULTS CONTROL PANEL CAUSE S E I D E M E R S The circulator is noisy LED on Suction pressure is insufficient cavitation Increase the system suction pressure within the permissible range LED on Presence of foreign bodies in the impeller Disassemble the motor and clean the impeller Loud noises of water circulation ...

Page 13: ...al operation activeADAPT 0 10V 5 s 8888 W GPM RPM FT CH E Parameters Meaning T 0 Display Firmware version T 1 Inverter Firmware version T 2 Unit of measurement shown on the display SI System International European IU Imperial units T 3 Maximum pump head T 4 Analog input voltage 0 10V T 5 Duty Cycle PWM input T 6 Mains voltage T 7 Internal inverter voltage T 8 Pump working hours in thousands 0 010 ...

Page 14: ... 14 NOTES ...

Page 15: ... 15 NOTES ...

Page 16: ...AW INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS IS IN EFFECT ONLY FOR THE DURA TION OF THE EXPRESS WARRANTY SET FORTH IN THE FIRST PARAGRAPH ABOVE THE ABOVE WARRANTIES ARE IN LIEU OF ALL OTHER WARRANTIES EXPRESS OR STATUTORY OR ANY OTHER WARRANTY OBLIGATION ON THE PART OF TACO TACO WILL NOT BE LIABLE FOR ANY SPECIAL INCIDENTAL INDIRECT OR CONSEQUENTIAL DAMAGES RESULTING FROM THE USE OF ITS P...