SPECIFICATIONS

Sensor

Temperature Sensor (TRP Series)

• Type: Precision thermistor 10K @ 77°F (25°C), Type III
• Accuracy: ±0.36 °F (0.2 °C)
• Range: -30 to 230°F (-34.4 to 110 °C)
• Humidity: 0 to 90% RH, non-condensing

General

Enclosure 

• Stainless steel (304 or 312)
• Dimensions: Probe 1” long x 0.25” dia (25.4 mm x 6.4 mm)

Weight and Wires

Wire Length 

• 500

 

feet max. (152.4

 

meters) between sensor and controller

TROUBLESHOOTING

This section provides useful tips on troubleshooting the iWorx® TRP Series Sensors.

Table 1: Troubleshooting Tips

Getting Help

Components within iWorx® TRP Series Sensors cannot be field repaired. If there is a problem with a sensor, follow the 
steps below before contacting your local TES representative or TES technical service.

1.Make sure sensors are connected and communicating to desired devices.
2.Record precise hardware setup indicating the following:

Version numbers of applications software.

Controller firmware version number.

A complete description of difficulties encountered.

Sensor

Wire Length 

(Apx.)

Wire Type

Sensor Weight

Ship Weight

TRP1

22.35-23 in (568-
584 mm)

22 AWG 7/30 white, stranded etched 
teflon rated to 392 °F (200 °C)

0.2 ounces  
(0.006 kilograms)

0.4 pounds  
(0.181 kilograms)

TRP2

130.5-131 in 
(3.31-3.32 m)

CLP2 2 conductor shielded plenum 
rated temp range -40 to 200°F (-40 to 
148.8°C)

0.12 pounds  
(0.054 kilograms)

0.5 pounds  
(0.227 kilograms)

Problem

Solution

Sensor reads 0 ohms

Sensor or wires are shorted together.

Sensor reads infinity 

Sensor or wires are open.

Erratic readings

Bad wire connection or condensation on board.

Summary of Contents for iWorx TRP Series

Page 1: ...Sensor 2 Overview 2 Features 2 Applicable Documentation 2 Installation Instructions 3 Precautions 3 General 3 Static Electricity 3 Location 3 Before Installing 3 About this Document 3 Inspecting the...

Page 2: ...via low cost shielded twisted pair cable Stainless steel probe Output 10K Ohm 77 F Applicable Documentation Model Total Length TRP1 24 inches TRP2 11 feet Description Audience Purpose iWorx TRP Series...

Page 3: ...a known securely grounded object to discharge any charge you may have accumulated Use a wrist strap when handling printed circuit boards The strap must be secured to earth ground Location Avoid locati...

Page 4: ...sensor WIRING INFORMATION The following electrical connection can be made to the iWorx TRP series sensors Wiring to the temperature inputs of iWorX controllers CAUTION Do not connect any power wiring...

Page 5: ...sensor follow the steps below before contacting your local TES representative or TES technical service 1 Make sure sensors are connected and communicating to desired devices 2 Record precise hardware...

Page 6: ...iWorx TRP Series Sensor 6 502 019 Effective October 17 2011 2011 Taco Electronic Solutions Inc Notes...

Page 7: ...iWorx TRP Series Sensor 502 019 Effective October 17 2011 7 2011 Taco Electronic Solutions Inc...

Page 8: ...this warranty TES products are not intended for use to sup port fire suppression systems life support sys tems critical care applications commercial aviation nuclear facilities or any other applica t...

Reviews: