When the
Temperature Differential Maximum
is set to 0, the
Supply Temperature Setpoint Reset Curve
is disabled and
the MPU2 operates with the usual heating and cooling supply air temperature setpoints.
Figure 7: Supply Air Setpoint Reset Curves
Heating Sequence
The controller provides support for either two stages of electric heating or one floating point or 0-10V modulating heat-
ing output (valve or variable speed circulator). You can specify which type of heat you are using through configuration
parameters.