iWorx® LCI3
8
502-050A, Effective: April 22, 2013
© 2013 Taco Electronic Solutions, Inc.
• Select ‘Ethernet Settings’ from the Network Setup screen
• Verify ‘Enable DHCP’ is set to Yes
• If set to NO, set to Yes and ‘Save’. Now Verify an IP address has been automatically placed in the following
fields; IP address, Subnet mask, Default Gateway, Primary DNS, Secondary DNS and External Gateway.
• Now that the IP addresses have been automatically set, disable DHCP (Set to NO). By setting this to “NO”
the LCI3 can always be accessed from the internet using this address.
4.Configure the router so the LCI3 can be accessed from the www
• Launch Internet Explorer or your preferred web browser
• Type http://192.168.1.1 in the address line and then press ‘enter’
• Enter the router password
• Select the ‘Application and Gaming’ tab. Other routers may have a ‘Setup’ or ‘Port Forwarding’ tab.
• Using one of the unused entries fill in the following information fields
• Application=LCI3
• Start=80
• End=80
• Protocol=TCP
• IP address=enter the external address as found in LCI3 or as supplied by an IT professional
• Enable=check the box and then save.
LCI3 QUICK-START ISP ETHERNET SET UP
Summary
Before beginning, please ensure that the LCI3 can be accessed by using the Internet. If the LCI3 has not yet been con-
figured for remote communications via the Internet please reference “Configuring Ethernet Communication” on page
5.
This section provides LCI3 Quick-start ISP setup instructions. It explains how to:
• Configure the LCI3 to communicate to an ISP
• Configure the LCI3 to send alarms via email
• Configure the LCI3 to selectively send emails
NOTE:
This section assumes that the LCI3 is already connected to the Internet.
Configuring an Email Proxy
The following procedure should be used only when there are multiple LCI3 controllers on the network, to configure
them to send all alarms through a single LCI3 controller. Disregard this section if there is only one LCI3 on the network.
Procedure
1.The following information is either chosen by you, your customer or provided by the ISP.
• Proxy Emailer – If multiple LCI3s are networked together and alarms are to be tunneled to a single LCI3 for
emailing, enter the LCI3s IP address or Site name in this field. This field is left blank if there are not multiple
LCI3s on the network.
2.The information field described in step 1 needs to be entered into the LCI3. To enter the information perform the
following.
• Sign-on to the LCI3
• Select ‘Utilities’ from the Home screen
• Select ‘Network Setup’ from the Utilities screen
• Select ‘Email Parameters’ from the Network Setup screen
• All fields with the exception of Proxy Emailer need to have valid information entered