iWorx® CSM1

502-045, Effective: July 25, 2013

© 2013 Taco Electronic Solutions, Inc.

Power (PWR)

Connect one output wire from a 24 VAC power supply to PWR (T39) and the other output wire from the power supply to 
the adjacent common terminal (T38).

Ground (GND)

Terminal GND

 

(T40) must be connected to earth ground. Failure to properly ground this equipment will 

result in improper operation. Improper grounding may also increase the risk of electrical shock, and may 
increase the possibility of interference with radio and TV reception.

SPECIFICATIONS

Electrical Inputs

Resolution:

 10

 bit 

Outside Air

 

Humidity, Inside Air Humidity, Supply Air Humidity:

 0-10

 Volts

 DC

Outside Air Temp, Hot Supply Water Temperature, Chilled Supply Water Temperature, Supply Air Temp:

 Precon 

Type III 10K thermistor

Energy

 Monitor, 

End

 of

 Interval:

 Normally open, Dry contact, 5

 

Volts DC Max

Unit Enable:

 Normally open (closed when active), Dry contact, 5

 

Volts DC Max

Recommended Sensor Wire 

Maximum Length:

 500 feet (152 meters) 

Recommended LON Bus FTT-10A Network Wire

Speed:

 78KBPS

Max Volts:

 42.4 Volts DC 

Cabling:

 Maximum node-to-node distance: 1312 feet (400 meters); Maximum total distance: 1640 feet (500 meters) 

Power

Requires:

 24VAC (20VAC to 28VAC), requires an external Class 2 supply

Consumes:

 7.2W with no external loads, maximum limited by the Class 2 supply rating

Mechanical

Dimensions:

 5.55” (141mm) high, 6.54” (166 mm) wide, 1.75” deep (44

 mm), 

ABS

Controller Weight:

 0.70

 pounds 

(0.32

 kilograms)

Shipping Weight:

 1.0

 pounds 

(0.46

 kilograms)

Processor:

 3150 Neuron 10 MHz

Flash:

 48

 Kilobytes 

Cable Type

Pairs

Details

Taco Catalog No.

18AWG 

1

Stranded Twisted Shielded Pair, Plenum

WIR-018

Cable Type

Pairs

Details

Taco Catalog No.

Level 4 22AWG (0.65mm)

1

Unshielded, Plenum, U.L. Type CMP

WIR-022

Summary of Contents for iWorx CSM1

Page 1: ...stallation Guide 4 General 4 Static Electricity 4 FCC Compliance 4 Before Installing 5 About this Document 5 Inspecting the Equipment 5 What is Not Included with this Equipment 5 Equipment Location 5...

Page 2: ...re measurement Outside air humidity measurement Supply water temperature measurement Inside humidity measurement Energy meter digital input for pulse counting Energy monitoring end of period digital i...

Page 3: ...n information about the Chilled Beam Sensor Module including sequence of operation and configuration information iWorx LCI Application Guide Document No 505 002 Application Engineers Installers Servic...

Page 4: ...connections in accordance with these instructions and in accordance with pertinent national and local electrical codes Use only copper conductors that are suitable for 167 F 75 C Static Electricity St...

Page 5: ...d humidity within the ranges specified for this equipment The equipment must be installed within 500 feet of all input peripherals smoke detectors sensors etc that are con nected to the equipment Sele...

Page 6: ...encil mark the mounting locations on the panel 3 Using a small drill bit pre drill the mounting holes 4 Using two 6 pan head screws mount the controller to the panel 5 Wire the controller See Routing...

Page 7: ...risk of electrical shock and may increase the possibility of interference with radio TV reception For best performance connect the power supply common terminal T38 to the same external point as the g...

Page 8: ...he adjacent common T4 The thermistor used must be 10K Precon Type III Chilled Supply Water Temperature CSWT To connect the Chilled Supply Water Temperature thermistor to the unit attach one wire from...

Page 9: ...thermistor Energy Monitor End of Interval Normally open Dry contact 5 Volts DC Max Unit Enable Normally open closed when active Dry contact 5 Volts DC Max Recommended Sensor Wire Maximum Length 500 fe...

Page 10: ...s of the controller s LEDs in the order they appear from left to right on the unit LED Indication Status Solid green when running and configured by an LCI networking Flashing green when running and NO...

Page 11: ...firmware version number A complete description of difficulties encountered Problem Solution Controller is not running and Status LED is not illuminated No power to controller Verify the voltage on th...

Page 12: ...red by this warranty TES products are not intended for use to sup port fire suppression systems life support sys tems critical care applications commercial aviation nuclear facilities or any other app...

Reviews: