12 - Setup and Operation

12.1 - Control (UI) Panel Layout

1

2

3

4

5

6

7

8

1.  Status LED

2.  Constant Pressure Mode Setting LED

3.  Constant Speed Mode Setting LED

4.  Proportional Pressure Mode LED

5.  0-10v Mode LED

6.  2 Pump Operation LED

7.  [^] Select Mode Button 

8.  [O]  Set Mode Button 

12.2 - Switching the Pump On and Off

When the pump is powered for the first time, it operates with the factory 

default setting in Constant Pressure mode equal to 45ft of head.

The pump requires dry contact to run and comes with a jumper across the 

ENABLE INPUT (J4) contacts found on the Control Panel UI.  The pump 

will run when connected to a power source when the jumper is connected.  

Turning the pump on/off remotely is accomplished by accessing the EN-

ABLE INPUT (J4) contacts on the UI control board located under the UI and 

connecting the contacts to an external relay.  Access is gained by removing 

the 4 screws located in each of the UI panel’s four corners.

13 - Pump Functions

[^] Select Mode Button

Short press: 

Change Mode

•  Scrolling through operational modes upwards. Current operation-

al mode LED blinking. To accept the new mode press the Set 

Mode button.  

Long Press – 

LOCKOUT

•  Pressing and holding the [^] Select Mode Button for 10 seconds 

activates or deactivates pump LOCKOUT. In LOCKOUT, the cur-

rently selected mode is active only. No changes can be made 

while in LOCKOUT. LOCKOUT activation or deactivation is ac-

knowledged by all LED’s blinking on/off 5 times.

[O] Set Mode Button

Short press: 

Confirm Selection

•  To  confirm  the  mode  currently  selected.    Selected  operational 

mode LED solid. 

NOTE:

 Pump returns to previous operational mode if Set Mode 

is not pressed.

[^] Select Mode [O] Set Mode Button

Long press (3 seconds): 

2 Pump Operation

•  To select or deselect 2 pump (lead/lag) operation.

13.1 - Pump Modes, 0-10Vdc and Parallel Pump Operation

The pump can operate in 9 different modes. Set the pump in the most ap-

propriate mode depending on the system where the pump operates.

The pump modes are: 

Constant Pressure:

 4 settings - 65ft, 45ft, 35ft, 25ft (Changes impeller 

speed to maintain pressure as flow increases)

•  The  pump  maintains  the  selected  pressure  from  0  flow  to  maximum 

power. At maximum power the pressure begins to drop.

Constant Speed:

 3 settings -  35ft, 25ft, 15ft (Maintains speed at selected 

head at 0 flow)

•  In Constant Speed mode the impeller speed is maintained through the 

entire range of flow.

Automatic Mode:

 1 setting (Proportional Pressure - increases impeller 

speed to increase differential head as flow increases)

•  In automatic mode the pump sets the operating pressure depending on 

the system resistance.

•  The parameters are preset and cannot be changed.   

0 – 10Vdc:

•  In this mode, all automatic curves are deactivated for full control via an 

external signal.  A dry contact from the external source is used to acti-

vate or deactivate the pump.  Pump speed is controlled via a 0-10V DC 

signal.  Loss of the 0-10V DC signal defaults pump to 50% of full speed.  

There is a 0-10V DC feedback signal to the BAS. 

To switch between modes (except 2-Pump Operation) depress the 

[^] Se-

lect Mode 

button for 1 second.  The selected mode LED will begin blinking. 

Continue pressing the 

[^] Select Mode 

button to scroll through the avail-

able modes indicated by the mode’s blinking LED.  Press the 

[O] Set Mode 

button to accept the desired operating mode.

2-Pump Operation:

 1 setting

•  This option is selected when 2 pump alternation is desired.

•  Pumps will alternate run-time every 24 hours (not adjustable).

•  In this mode the lead pump will control the operation of the lag pump.

1.  Set both pumps to the same Mode

2.  Turn main power off to both pumps

3.  Connect Primary Pump “P1” relay output common and NO to  

 

“P2” Enable Input (see 21.1 - Connection Examples Parallel   

 

Pump Operation).  NOTE:  Remove factory installed jumper 

 

from “P2” Enable Input

4.  Connect “P2” 0 – 10Vdc Output to “P1” 0-10Vdc Input, positive 

 

to positive and negative to negative

5.  NOTE:  Between pump standard 18ga unshielded 

 

communication wire is sufficient

To activate or deactivate 2-Pump Operation, press the 

[^] Select Mode 

button

 + [O] Set Mode 

button together and hold for 3 seconds. The 2-Pump 

Operation LED will light indicating 2-Pump Operation activation. The LED 

will go out upon deactivation.

wire is present, a red wire is a sec-

ondary live wire found in some 220/1 

circuits.  Connect the white wire of 

the pump to the white or gray neutral 

wire of the system.  The installation 

green ground wire is connected to the 

grounding terminal inside the pump 

electrical box. See fig 2 noted to the 

left.

Figure 2

Electrical opening: ½” 14 MPSM standard thread

Summary of Contents for 1900e Series

Page 1: ...SUPERSEDES NEW Effective January 21 2019 302 388 Plant ID No 001 5016 Instruction Sheet 1915e ECM Circulator...

Page 2: ...Connections Setup and Operation Control UI Panel Layout Switching On Off Pump Functions Mode Descriptions Specifications Application Electrical Ratings Standards Protection Connections Materials of Co...

Page 3: ...chaudes peuvent provo quer des br lures Le moteur peut galement atteindre des temp ratures qui peuvent entra ner des blessures Warning The addition of petroleum based fluids or certain chemical additi...

Page 4: ...l position or the vertical position with the control module facing up see Figure 1 The cover can be rotated independent of the pump to adjust orientation of the User Interface the cable glands should...

Page 5: ...g and Impeller Motor assembly Using the new gasket provided with the seal kit reassemble the Impeller Motor assembly to the casing and secure with the four body bolts Use caution not to pinch the body...

Page 6: ...he pressure begins to drop Constant Speed 3 settings 35ft 25ft 15ft Maintains speed at selected head at 0 flow In Constant Speed mode the impeller speed is maintained through the entire range of flow...

Page 7: ...tection electronically protected Continuous Duty UL778 1004 1 508C CAN CSAC22 2 108 100 107 1 EMC 89 366EEC EN61000 Flange Connections 2 bolt 17 Materials of Construction Casing Impeller Shaft Bearing...

Page 8: ...external controller MOTOR CONTROLLER RIBBON CABLE Connects High Voltage Power Module to UI If the cable becomes disconnected reconnect to MOTOR CONTROL RIBBON CABLE connector 21 Connection Considerat...

Page 9: ...l 3 2 PUMP OPERATION Lead Pump 2 PUMP OPERATION Lag Pump Analog Control Curve RUN Voltage MAX Voltage Function 1 V 3 V Pump at minimum speed 0 V 2 V Pump is at 1 2 speed 3 V 3 to 10 V Speed is proport...

Page 10: ...n effect at time of factory examination and repair Any Taco product or part not installed or operated in conformity with Taco instructions or which has been subject to misuse misapplication the additi...

Reviews: