4. Wiring the circulator: Disconnect the AC power supply. Remove the
terminal box cover. Attach a wiring connector into the knockout hole.
Use a flexible conduit only. Connect Line/Hot power to the black lead,
neutral to the white lead. See wiring diagram to the right. Replace the
terminal box cover.
Note: If pigtail leads provided are not used, be sure to trim field wire to a
strip length of .25" (+/- .025") to prevent exposed wire causing a short at the
terminal plug. Connect line and neutral to green terminal plug as shown in
the Wiring Diagram. Depress the spring tab with a small screwdriver to
insert wire into the plug. Release tabs to complete connection. The 007e-2
is a double insulated circulator. No grounding wire is necessary.
5. Start the circulator: When purging the system, it is recommended to
run the circulator long enough to remove all remaining air from the
bearing chamber. This is especially important when installing the circu-
lator in the off-season. An orange LED will illuminate when the 007e-2
is powered on.
6. Green Mode: Responsive technology actively monitors system condi-
tions and automatically adjusts to optimize power consumption. In this
mode the LED changes to green.
CAUTION: Never run the circulator dry or permanent damage may result.
ATTENTION: Ne laissez jamais le circulateur tourner à sec, des dommages permanents peuvent en résulter.
CAUTION: Do not attempt to remove LED panel from circulator. Serious damage to circulator electronics may result.
ATTENTION: N'essayez pas de retirer le panneau de LED du circulateur. Des dommages sérieux à l'électronique du circulateur
peuvent en résulter.
Orange LED
Green LED
Proportional
Pressure Mode
007e-2 Performance Curves
Green Mode: After 7 days of constant circulation, the 007e will self-adjust to Green Mode curve (low proportional pressure)
for power optimization. See Green mode curve above. When the 007e-2 cycles OFF, the circulator resets to original Normal
Mode curve.
Normal Mode
Green Mode
-5-