DESCRIPTION:

The 0026e™ is a high-performance, variable speed, high-efficiency, wet-rotor circulator 

with an ECM permanent magnet motor. With 5 easy settings, its variable speed 

performance curves are equivalent to the Taco 0010, 0011, 0012, 0012 3-Speed,

0013, 0013 3-Speed & 0014. Ideal for large residential and light commercial hydronic 

heating, chilled water cooling and domestic hot water systems. The 0026e reduces 

power consumption by up to 85% compared to equivalent AC permanent split 

capacitor circulators. With a maximum of 26 feet of head and 44 gpm. It is available

in either Cast Iron or NSF certified Stainless Steel.

APPLICATION:

• Maximum operating pressure: 150 psi (10.3 bar)

• Maximum fluid temperature: 230°F (110˚C)

• Minimum fluid temperature: 14°F (-10˚C)

• Electrical specifications:

Voltage: 115/208/230V, 50/60 Hz, single phase

Maximum operating power: 120W

Maximum amp rating: 1.05 A

• Equipped with a Cast Iron or Stainless Steel casing

• SS Model suitable for open loop potable water systems

• Taco circulators are for indoor use only – employer uniquement a l’interieur

• Acceptable for use with water or maximum of 50% water/glycol solution

FEATURES:

• 5 easy dial settings to match system requirements - activeADAPT, LOW, MEDIUM, HIGH or 0-10V DC input

• Replaces all single speed and 3-speed circulators in its class

• ECM performance equivalent to Taco’s 0010, 0011, 0012 & 0014 circulators

• Multi-color LED: power on, mode setting and error code diagnostics

• Use with a Taco ZVC Zone Valve Control or SR Switching Relay for ON/OFF operation

• Nut-capture feature on flanges for easier fit up

• Dual electrical knockouts and removable quick-connect terminal strip for easy wiring

• Whisper quiet operation

BIO Barrier®

 protects the pump from system contaminants

SureStart®

 automatic unblocking and air purging mode

• Rotatable control cover to allow any pump body orientation

INSTALLATION:

WARNING: Do not use in swimming pool or spa areas. Pump has not been investigated for these applications.

AVERTISSEMENT : Ne pas utiliser dans une piscine ou un spa. La pompe n’a pas été étudiée pour ces applications.

CAUTION: The addition of petroleum based fluids or certain chemical additives to systems using TACO equipment

voids the warranty. Consult factory for fluid compatibility.

ATTENTION : L’ajout de liquides à base de pétrole ou de certains additifs chimiques à des systèmes utilisant un

équipement TACO annule la garantie. Consultez le fabricant pour connaître la compatibilité de liquides.

CAUTION: Installations at elevations over 5000 feet must have higher fill pressure of 20 psi minimum to prevent

pump cavitation and flashing. Premature failure may result. Adjust expansion tank pressure to equal fill pressure. 

A larger size expansion tank may be required.
ATTENTION : Des installations à des altitudes de plus de 1600 mètres doivent présenter une pression de remplissage plus élevée de 20 psi 

au minimum afin d’éviter toute cavitation ou flashing de la pompe. Une défaillance prématurée peut en résulter. Réglez la pression 

du réservoir d’expansion de façon qu’elle soit égale à la pression de remplissage. Un réservoir d’expansion d’une taille supérieure 

peut être nécessaire.

Instruction Sheet

102-566

SUPERSEDES: 

October 27, 2020

EFFECTIVE: February 1, 2021

Plant ID No. 001-5032

-1-

Figure 1

Standard flange model: 0026e-F2

Certified to

NSF/ANSI 61 & 372

Summary of Contents for 0026e

Page 1: ...ier fit up Dual electrical knockouts and removable quick connect terminal strip for easy wiring Whisper quiet operation BIO Barrier protects the pump from system contaminants SureStart automatic unblocking and air purging mode Rotatable control cover to allow any pump body orientation INSTALLATION WARNING Do not use in swimming pool or spa areas Pump has not been investigated for these application...

Page 2: ...NE 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 FC FC Optional Location FC FC ZONE 1 ZONE 2 ZONE 3 FC FC Optional Location FC FC V3 V3 V3 V2 V2 V2 P P P EXPANSION TANK V1 V1 PV4 P EXPANSION TANK BOILER EXPANSION TANK BOILER V3 V2 P V3 V2 P V3 V2 P V3 V2 P V3 V2 P V3 V2 P V1 PV4 V1 Figure 2 PREFERRED PIPING FOR CIRCULATORS ON BOILER SUPPLY PREFERRED PIPING FOR CIRCULATORS ON BOILER RETURN PREFERRED PRIMARY...

Page 3: ...NE 3 ZONE 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 KEY V1 V2 V3 SHUT OFF ISOLATION VALVE P TACO 0026e CIRCULATOR FF FAST FILL BOILER FEED VALVE PV4 PURGE VALVE ZV ZONE VALVE MOD CON BOILER EXPANSION TANK EXPANSION TANK BOILER EXPANSION TANK BOILER Figure 3 PREFERRED PIPING FOR ZONE VALVES ON BOILER SUPPLY ALTERNATE PIPING FOR ZONE VALVES ON BOILER RETURN PREFERRED PRIMARY SECONDARY PIPING FOR ZONE VAL...

Page 4: ...he system will result in immediate lubrication of the bearings It is always good practice to flush a new system of foreign matter before starting the circulator WARNING Risk of electric shock To reduce the risk of electric shock be certain that it is connected only to a properly grounded grounding type receptacle Follow all local electrical and plumbing codes AVERTISSEMENT Risque de choc électriqu...

Page 5: ...hecirculatorfor0 10VDCOperation See Page 9 5 Start the circulator When purging the system it is recommended to run the circulator at full speed long enough to remove all remaining air from the bearing chamber This is especially important when installing the circulator in the off season Turn the dial to the HIGH setting for maximum fixed speed A blue LED will illuminate when the 0026e is powered on...

Page 6: ...t on back page The 0026e has 5 Operating Settings activeADAPT Automatic self adjusting proportional pressure variable speed Violet LED LOW 8 feet of head constant pressure variable speed Orange LED MEDIUM 16 feet of head constant pressure variable speed Orange LED HIGH 26 feet of head max full fixed speed Blue LED 0 10V DC Analog external input or PWM pulse width modulation input from building con...

Page 7: ... 16 18 20 22 24 26 28 30 32 34 36 38 50 40 42 44 46 48 Flow Rate Q GPM 0 4 6 2 8 10 12 14 16 18 20 22 24 26 28 Head ft 6 0026e High Efficiency Circulator activeADAPT Range Purple LED activeADAPT activeADAPT Mode activeADAPT is an operating mode designed for constant circulation systems On this setting the circulator will sense changes in system flow and head conditions and adjust the operating cur...

Page 8: ...gh Efficiency Circulator Maximum Curve Fixed Speed Blue LED 2 0 Flow Rate Q GPM 0 2 4 6 8 10 12 Head ft 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 14 16 18 20 22 24 26 28 HIGH Head 26 ft 0026e High Efficiency Circulator Maximum Curve Fixed Speed Blue LED Fixed Speed Mode At High setting the circulator always operates at full speed ...

Page 9: ...or external signal wiring 3 Disconnect the connector 4 from control board 5 4 Insert the cable 6 into the cable gland M12x1 5 7 and screw it to the cover 5 Strip the wires 5 mmMIN and insert them into the connector 4 then secure them with the screws 8 6 Re connect the connector 4 to the electronic board close the cover and secure it with the screws Figure 8 External connection for 0 10V DC PWM sig...

Page 10: ... 10V DC analog signal external input PWM Pulse Width Modulation 2V 4V 6V 8V 10V 0 140 100 120 80 40 20 60 2 0 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 Head ft 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 0 10V 0 10V Power W 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 0 Flow Rate Q GPM Flow Rate Q GPM 0026e High Efficiency Circulator 0 10V DC Perfor...

Page 11: ...e replaced FAULTS CONTROL PANEL CAUSE S E I D E M E R S The circulator is noisy LED on Suction pressure is insufficient cavitation Increase the system suction pressure within the permissible range LED on Presence of foreign bodies in the impeller Disassemble the motor and clean the impeller Loud noises of water circulation Flashing white LED Air in the system Circulator may be air bound Vent the s...

Page 12: ...f its products without notification TACO OFFERS THIS WARRANTY IN LIEU OF ALL OTHER EXPRESS WARRANTIES ANY WARRANTY IMPLIED BY LAW INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS IS IN EFFECT ONLY FOR THE DURA TION OF THE EXPRESS WARRANTY SET FORTH IN THE FIRST PARAGRAPH ABOVE THE ABOVE WARRANTIES ARE IN LIEU OF ALL OTHER WARRANTIES EXPRESS OR STATUTORY OR ANY OTHER WARRANTY OBLIGATION ON THE PA...