TAC Xenta, TAC Xenta® 400 I/O Modules
4 Installation
TAC AB, Dec 2004
43 (48)
0-004-7771-3 (EN)
TAC Xenta 400 input/output cable requirements
Terminals type X:
Min. cross-sectional area................................ 0.25 mm² (22 AWG)
Max. cable length .................................................... 200 m (660 ft.)
Terminals type U, connected as
a) digital inputs,
b) measurement devices using voltage signals that are
not
powered via the same transformer as the I/O module or
c) measurement devices using current signal
Min. cross-sectional area................................ 0.25 mm² (22 AWG)
Max. cable length .................................................... 200 m (660 ft.)
Terminals type U, connecting measurement devices, using voltage
signals that are powered via the
same
transformer as the
I/O module:
Min. cross-sectional area................................ 0.75 mm² (19 AWG)
Max. cable length ........................................................ 20 m (66 ft.)
Fig. 4.18: Connecting the communication cable
TAC Xenta 1
C1 C2
C1 C2
C1 C2
C1 C2
TAC Xenta 1
TAC Xenta 2
TAC Xenta 2
470 k
Ω
¼ W
Communication cable,
unshielded
Communication cable,
unshielded
Terminals for
incoming cables
Terminals for
incoming cables
Shield is grounded
at one point only
Separate
junction
Summary of Contents for Xenta 400 Series
Page 1: ...TAC Xenta TAC Xenta 400 I O Modules...
Page 2: ......
Page 3: ...TAC Xenta TAC Xenta 400 I O Modules...
Page 6: ...Contents TAC Xenta TAC Xenta 400 I O Modules 6 48 TAC AB Dec 2004 0 004 7771 3 EN...
Page 7: ...INTRODUCTION 1 Introduction...
Page 8: ......
Page 11: ...REFERENCE 2 I O Modules in the TAC Xenta 400 series 3 Technical Description 4 Installation...
Page 12: ......
Page 47: ......