![TAC Xenta 400 Series Manual Download Page 24](http://html1.mh-extra.com/html/tac/xenta-400-series/xenta-400-series_manual_3165626024.webp)
3 Technical Description
TAC Xenta, TAC Xenta® 400 I/O Modules
TAC AB, Dec 2004
0-004-7771-3 (EN)
3.5
TAC Xenta 451/452 Analog Input and Output
module
The modules have four universal inputs, four thermistor inputs and two
analog outputs. The universal inputs can be used as analog inputs, dig-
ital inputs or pulse counters.
The TAC Xenta 452 is also equipped with LED status indicators, one
for each universal input, when used as a digital input, and manual over-
ride controls for the analog output values. The LED input status colors,
red or green, can be selected individually by setting switches under the
front cover.
Terminals (451, 452) and Controls/Indicators (452)
Fig. 3.6: TAC Xenta 451/452 terminals and TAC Xenta 452 Analog output override controls and Indicators
MAN 1
AUTO
MAN 2
AUTO
1 2 3 4
AO
0 - 10V
TAC Xenta 452
0 - 10V
DI
1 2 3 4 5 6 7 8 9 10
11 12 13 14 15 16 17 18 19 20
G G0 C1C2 U1 M U2 U3 M U4
Y1 M Y2 B1 M B2 B3 M B4
UI
~ 0
24 V AC/DC
}
Comm
}
AO
Thermistor inputs
2 Analog outputs:
Override controls
4 DI Indicators:
⇑
red
⇓
green
Table 3.4: TAC Xenta 451/452 summary
Type
No.
TAC Menta Block type
Terminal ref.
Ind./Override (452)
Thermistor inputs
4
AI - Analog input
B1 - B4
-
Universal inputs
4
AI - Analog input
or
DI - Digital input
or
CNT - Pulse counter
U1 - U4
U1 - U4
U1 - U4
-
red or green / -
-
Analog outputs
2
AO - Analog output
Y1 - Y2
- / Man-Auto
Summary of Contents for Xenta 400 Series
Page 1: ...TAC Xenta TAC Xenta 400 I O Modules...
Page 2: ......
Page 3: ...TAC Xenta TAC Xenta 400 I O Modules...
Page 6: ...Contents TAC Xenta TAC Xenta 400 I O Modules 6 48 TAC AB Dec 2004 0 004 7771 3 EN...
Page 7: ...INTRODUCTION 1 Introduction...
Page 8: ......
Page 11: ...REFERENCE 2 I O Modules in the TAC Xenta 400 series 3 Technical Description 4 Installation...
Page 12: ......
Page 47: ......