Application

The TC-5231, TC-5232, and TC-5241 low temperature 
thermostats are used to control temperature in air 
conditioning or refrigeration systems. The low 
temperature thermostat measures the coldest one-foot 
section along the entire 20-foot sensing element.

The low temperature thermostats are applicable to 
various applications such as: low temperature control 
of steam coils; frost indication in storehouses or 
orchards; temperature control of freezer cabinets, 
display cases, beverage coolers, milk cooling tanks, 
and air conditioners.

Features

20 ft. (6.1 m) element senses temperature over a 
large area. Control responds to coldest one-foot 
section of the sensor.

Adjustable setpoint from 35 to 60°F (1.7 to 15.5°C) 
with 5°F (3°C) fixed differential.

SPDT and DPST versions.

Rated for use at 17 full load amps (120/208/240 
Vac), 24 non-inductive amps (120/208/240 Vac), 
and 16 non-inductive amps (24 Vac). Capable of 
controlling refrigeration equipment directly.

UL and CSA approved.

Capillary clips provided.

Applicable Literature

TAC Electric/Electronic Products Catalog, F-27382

Environmental Controls Application Manual, 
F-21335

Low Temperature Thermostats 

General Instructions

TC-5231 Series, TC-5232, 

& TC-5241 Series

Invensys

Summary of Contents for TC-5231 Series

Page 1: ...ture control of freezer cabinets display cases beverage coolers milk cooling tanks and air conditioners Features 20 ft 6 1 m element senses temperature over a large area Control responds to coldest on...

Page 2: ...rmal Sensing Element 0 to 100 RH Enclosure Rating NEMA Type 1 Dimensions Case 2 7 H x 3 44 W x 1 97 D in 69 x 87 x 50 mm Element 3 32 in O D x 20 ft length 2 4 mm x 6 1 m Agency Approvals UL 873 Tempe...

Page 3: ...Motor 3 1 1 Terminals 2 and 1 close on temperature drop 1 Temp Drop Figure 1 TC 5231 and TC 5241 Typical Application AC Supply L L Fan Motor T T Indication Circuit Note Contacts are not rated for dry...

Page 4: ...s in accordance with the wiring diagram and in accordance with the National and Local Electrical Code Use copper conductors only Do not restore electrical power until installation is complete T C A U...

Page 5: ...ure the element into place using the five capillary clips provided 6 Remove the cover See Figure 4 7 Mount the case with two screws 10 maximum in the screw slots in the back of the case See Figure 6 8...

Page 6: ...grounding screw provided on the TC 52xx case to connect the unit to earth ground 3 Loosen the terminal screws and make the appropriate power wiring connections to the numbered terminals The TC 52xx ca...

Page 7: ...l push the manual reset button to put the thermostat into service Manual Operation of Switch T C A U T I O N When the sensed temperature is below setpoint the switch is open terminals 2 3 on TC 52x1 a...

Page 8: ...nge without notice F 25911 5 www tac com TAC 1354 Clifford Avenue P O Box 2940 Loves Park IL 61132 2940 DIMENSIONAL DATA Dimensions are shown in inches millimeters Figure 6 TC 52xx Mounting Dimensions...